SQUARE BODY MONOBLOCK GAS BURNERS
INSTALLATION, OPERATING AND
MAINTENANCE MANUAL
ONE STAGE AND TWO-STAGE OPERATION
ECO 1.0
ECO 2.0
ECO 30.0

Questions and Answers

  • M
    Mark LunaAug 11, 2025
    What to do if my ECOSTAR Burner starts up, but fails after 30 seconds?
    • E
      Emma CortezAug 11, 2025
      If your ECOSTAR Burner starts but then fails after 30 seconds, the gas valve might be closed, or the supply gas pressure could be low; check the gas inlet manometer. Also, the ignition electrodes might be misadjusted, or the ignition cables may have come loose. Adjust the ignition electrodes, ensuring a 3-5 mm gap between them. Finally, verify the starting setting of the gas valve to ensure sufficient gas flow for burner activation.
  • H
    Hailey BrooksAug 18, 2025
    What to do if my ECOSTAR ECO 1.0 Burner flame appears and goes into failure mode?
    • E
      evan86Aug 18, 2025
      If the flame appears and then the ECOSTAR Burner goes into failure mode, it could be due to a gas pressure error; the supply gas pressure might be low. Another cause may be a faulty or contaminated ionization electrode; remove and clean it. Finally, the program relay may have failed; replace it with a new one.
  • V
    Vanessa MoralesAug 23, 2025
    What to do if my ECOSTAR ECO 1.0 cannot be commissioned?
    • B
      Brenda SparksAug 23, 2025
      If your ECOSTAR Burner cannot be commissioned, consider the following potential causes and solutions: * The gas valve might be closed or gas supply cut. Open the valve. * There might be a fuse failure. Check the burner power supply, including the main panel and burner fuses. * The thermal relay could be faulty. Reset the thermal relay and check its adjustment according to the current indicated on the motor label. Replace it if the problem persists. * Boiler thermostat or pressure switch failure. If there's an issue with the burner thermostats, pressure switches, or steam tank, it might stem from an unadjusted or faulty water level device; adjust or replace it.
  • B
    bensonseanAug 29, 2025
    Why does my ECOSTAR ECO 1.0 Burner start up, but fail after 10 seconds?
    • J
      John JamesAug 30, 2025
      If your ECOSTAR Burner starts but fails after 10 seconds, the air pressure switch might be adjusted too high, or it may be dirty or broken. Also, the program relay may have failed, requiring replacement. Check the fan motor coils, motor contactor, and the outlet from the program relay.
  • T
    Tracy JosephSep 4, 2025
    How to fix an overheating ECOSTAR Burner boiler cover?
    • J
      Jorge ChaneySep 5, 2025
      If the boiler cover is overheating, ensure proper sealing between the boiler cover and the burner. If necessary, use insulating material between the boiler connecting flange and the boiler cover.