To ensure proper operation of the sprinkler system and the nitrogen generator, calibrate the sprinkler
system operating pressure to the turn-on and turn-off pressure of the nitrogen generator using the Air
Maintenance Device (AMD) Pressure Adjustment Procedure in the Maintenance Section of this manual.
The procedure aligns the sprinkler system operating pressure to the turn-on pressure of the nitrogen
generator; reducing the potential of the nitrogen generator turn-on pressure to be set near the low-air
alarm/trip pressure of the sprinkler system.
Sprinkler System Air Maintenance Device
Dry pipe and preaction fire sprinkler systems are to be configured to use a single air maintenance device
(AMD) for each dry pipe or preaction fire sprinkler system in accordance with NFPA 13.
• Applications where multiple fire sprinkler systems are served with a single AMD has been known
to cause nitrogen generators to short cycle due to the air restriction that the AMD imposes on the
nitrogen supply line. Short cycling of the nitrogen generator can cause damage to the system
components and may affect the manufacturer’s warranty.
AMD operation is directly affected by the inlet pressure to the AMD. To ensure the AMD operates properly
with the nitrogen generator, use the Air Maintenance Device (AMD) Pressure Adjustment Procedure in
the Maintenance Section of this manual.
Fire Sprinkler System Leak Rates
The leak rate of a dry pipe or preaction fire sprinkler system will have a direct effect on the nitrogen
generator run frequency or on/off cycles. The maximum allowable leak rate in a fire sprinkler system as
defined by NFPA 13 is 1.5 psig (.1 bar) within a 24-hour period. The design specifications of ECS nitrogen
generator is based on 6.0 psig (.4 bar) leak rate within a 24-hour period. Sprinkler systems with a leak rate
in excess of 6.0 psig (.4 bar) within a 24-hour period will cause the nitrogen generator run frequency to
increase resulting in a greater wear on system components and a potential reduction in the service life of
the nitrogen generator. Sprinkler systems with a leak rate greater than 6.0 psig (.4 bar) in 24-hours need
to be repaired to ensure the anticipated service life of the nitrogen generator is met.
NOTES: The run frequency of the nitrogen generator in this chart is based on nitrogen generator
operation outside of the 14-day nitrogen inerting process with the vent closed.
Excessive cycle count could indicate an air compressor/nitrogen generator short cycling issue. Contact
ECS immediately.