52
Maintenance
SAFETY WARNING
Only qualified personnel can perform inspection, testing and maintenance of the nitrogen generation
equipment. Prior to any system maintenance on the nitrogen generation system, ensure that the nitrogen
generator is isolated from the compressed air supply and all system risers. Ensure that the nitrogen
generation system and the associated piping that is to be manipulated is completely depressurized prior
to performing any maintenance. Failure to do so can result in system damage and/or personal injury.
MAINTENANCE and TROUBLESHOOTING WARNINGS
1. Nitrogen Generator includes 120-240VAC/50-60 Hz voltage inside cabinet. Exercise caution and
do not touch any wiring connections when power is applied to the unit.
2. Nitrogen Generator has hot surfaces inside cabinet when nitrogen generator is operating and
after nitrogen generator has turned off. Exercise caution when working on nitrogen generator
while operating and after nitrogen generator has shut off. (Wear Hand Protection, where needed)
Routine Checks
The nitrogen generators require limited maintenance; however, it is advisable to routinely check the
generator to ensure functionality. The following is a checklist and schedule for routine inspection.
Check
Occurrence
Verify all valves have smooth operation - clean and un-corroded
Quarterly
Verify all manual valves fully open and close
Quarterly
Verify compressor is turning on/off at low/high pressure
Quarterly
Verify correct nitrogen purity level out of cabinet sampling port
Quarterly
Verify pressure gauges are in working order
Quarterly
Verify there are no noticeable leaks on unit
Quarterly
Check coalescing filters
Semi-annually
Check for loose connections in cabinet and control box
Semi-annually
Check compressor filter
Semi-annually
Replace coalescing filters
Annually
Verify Oxygen Removal Vent In-Line Filter and Y-Strainer are clean
Annually
Verify no air or water leaks in Oxygen Removal Vent
Annually
HMI User Interface Information
The nitrogen generator operation is accomplished through the Human Machine Interface (HMI) screen.
The HMI screen provides access for setup, monitoring and control functions of the nitrogen generator. All
of the screens on the HMI are accessible from the Home Screen.