COMMISSIONING CHECKLIST
Fire Sprinkler System - General
Verify and document the quantity of dry/preaction fire sprinkler systems connected to the nitrogen
generator: Yes Qty. _________
Verify and document the capacity of each dry/preaction fire sprinkler systems connected to the nitrogen
generator (gallons or sq. ft.): Yes
Sys. #1 _________________ Sys. #9 _________________ Sys. #17 _________________
Sys. #2 _________________ Sys. #10 _________________ Sys. #18 _________________
Sys. #3 _________________ Sys. #11 _________________ Sys. #19 _________________
Sys. #4 _________________ Sys. #12 _________________ Sys. #20 _________________
Sys. #5 _________________ Sys. #13 _________________ Sys. #21 _________________
Sys. #6 _________________ Sys. #14 _________________ Sys. #22 _________________
Sys. #7 _________________ Sys. #15_________________ Sys. #23 _________________
Sys. #8 _________________ Sys. #16_________________ Sys. #24 _________________
Verify and document the make and model of air maintenance device(s): __________________________
Verify and document the pressure settings of the air maintenance device(s): _______________________
Verify and document the Systems(s) High Air Alarm Pressure: __________________________
Verify and document the Systems(s) Low Air Alarm Pressure: __________________________
Verify and document the Systems(s) Trip Pressure: __________________________
Verify and document the make and model of accelerator: __________________________
Air Compressor - Existing
Verify and document the location of the air compressor: __________________________
Verify and document the manufacturer of the air compressor: __________________________
Verify and document the model number of the air compressor: __________________________
Verify and document the serial number of the air compressor: __________________________
Verify and document the air compressor on/off pressure settings: __________________________
Verify and document if an air compressor exists and whether the existing air compressor(s) to remain:
Yes No
If existing Yes: Primary Backup Meet NFPA 13 30-Minute Fill Requirement
Verify and document whether the fire sprinkler system(s) are supplied by house air: Yes No
If Yes, what pressure: ________