EasyManua.ls Logo

ECU ECU-57N - Remote Standby Operation; Standby Mode Functionality; Engine Crank Cycle; Crank Mode Initiation

ECU ECU-57N
7 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
REMOTE
STANDBY
FUEL
RELAY
START RELAY
HIGH WATER TEMP
LOW OIL
PRESS
MAGNETIC
PICKUP
REMOTE
START
CONTACTS
6
5
4
3
1
15
14
13
X1
FOR
INFORMATION
ON
SETUP
OF
POTS
AND
SWITCHES
SEE
ADJUSTMENTS
PAGE
AUTO
OFF
MANUAL
LOW OIL
PRESSURE
LAMP
HIGH WATER TEMP LAMP
OVERCRANK
LAMP
OVERSPEED
LAMP
ENGINE STARTED LAMP
COMMON
ALARM
LAMP
In
the
Standby
mode
the
Engine
Control
Switch
is in the
Auto
position
as
the
module
monitors
the Remote
Start
Contacts.
All
that
is required
for
cranking
to
begin is
the
closure
of
the Remote
Start
Contacts
shown
connected across terminals
13
and
14.
ENGINE
CRANK
CYCLE
FUEL
RELAY
START RELAY
HIGH WATER TEMP
LOW OIL
PRESS
MAGNETIC
PICKUP
REMOTE
START
CONTACTS
15
14
13
X1
6
5
FOR
INFORMATION
4
ON
SETUP
OF
POTS
AND
3
SWITCHES
SEE
ADJUSTMENTS
2
PAGE
1
AUTO
OFF
MANUAL
LOW OIL PRESSURE LAMP
HIGH WATER TEMP LAMP
OVERCRANK
LAMP
OVERSPEED LAMP
ENGINE STARTED LAMP
COMMON
ALARM
LAMP
Closure
of
the
Remote
Start
Contacts
while
in
AUTO
initiates
the
Crank
mode.The
Fuel Relay and Starter Relay
are energized causing
the
engine
to
begin cranking. The Crank mode will
continue
for
the duration
of
the
settings
of
the
Crank Cycle
Adjust
and
the
Dip
Switch,
unless Overcrank occurs
first.
During
the
Engine Crank
Cycle
the
Low
Oil Pressure
Switch
is ignored. To set Cycle Time and Crank
Attempts
see
adjustments
page.