P/N P-047550-1788-EN • REV 013 • ISS 08SEP19 3 / 3
Specifications
Operating voltage 15.20 to 19.95 VDC
Current
Standby
Alarm
170 µA
170 µA
Circuit resistance between
isolators
6 Ω max.
Ground fault impedance 10 kΩ
Circuit designation
Signaling line circuit
Class A, Class X
Wire size 12 to 18 AWG (1.0 to 4.0 mm²)
Compatible electrical boxes
2-1/2 in. (64 mm) deep double-gang
box; 4 in. square box, 1-1/2 in. (38
mm)
deep with double-gang cover
Operating environment
Temperature
Relative humidity
32 to 120°F (0 to 49°C)
0 to 93% noncondensing
Storage temperature range −4 to 140°F (−20 to 60°C)
Regulatory information
FCC compliance
This device complies with part 15 of the FCC
Rules. Operation is subject to the following two
conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any
interference received, including interference that
may cause undesired operation.
Contact information
For contact information, see www.edwardsfiresafety.com.