42
If the selected installation type is hydraulic (see 3.2), the
Antifreeze temperature must be above 16°C in order to reduce
the probability of condensation forming in the pipes.
Note: Antifreeze Protection operates even when the chronothermostat is “off”.
This protective functionality switches the Heating system “on” when the ambient
temperature reaches the minimum temperature set.
3.6.2 Overheating Protection (overheating protection temperature
can only be set when in cooling mode)
Press or to select the desired Overheating Protection
temperature (+0,5°C to 35,0°C) press OK to confirm and exit or
to go back. (Default setting: 30,0°C).
Note: Protection against overheating operates even when the chronothermostat
is “off”. This protective functionality switches the Cooling system “on” when the
ambient temperature reaches the maximum temperature set.
3.7 Differential temperature
Press or to select the desired differential temperature (0,5°C to
3,0°C). Press OK to confirm and exit or to go back. (Default setting:
1,0°C).
3.8 Temperature Monitoring (select the temperature monitoring
sensor)
Press
or to navigate between options (Ambient Sensor, Floor Probe
or Ambient Sensor + Floor Probe). Press OK to select or to go back.
Note: When the chronothermostat is “on”, Floor Probe is automatically detected. In
the event of a Probe error, an error message will appear on the chronothermostat.