7
Output Voltage Low
Incorrect connections.
Voltage adjust turned down.
Remote voltage adjust is turned down.
Defective regulator.
Check wiring diagram for proper
connections.
Incorrect sensing voltage connection can
cause output voltage low-no adjustment.
Rotate voltage adjust CW until desired
voltage is reached.
Rotate remote voltage adjust CW until
desired voltage is reached.
Replace regulator.
Output Voltage High
Voltage adjust turned too high.
Remote voltage adjust is turned too
high
Rotate voltage adjust CCW until desired
voltage is reached.
Rotate remote voltage adjust CCW until
desired voltage is reached.
Output Voltage High-
No Adjustment
Defective regulator. Replace regulator.
Rating Output
Voltage at no load and
Voltage Down at load
condition
Generator defective Check the generator exciter and rotating
diode
Remote voltage Adjust
Operates backwards
Voltage adjust wire backwards. Reverse the wiring of the connection on
the remote voltage adjust.
Generator Output
Voltage Hunting
Defective regulator Rotate the stability adjust in a CW
direction until hunting stops
Poor Regulation
Defective regulator. Replace regulator.