Table 3 - EIB650i INDICATOR SUMMARY
Table 3 - EIB650i INDICATOR SUMMARY (cont.)
Normal Operation
Action
Power up Twist on base1 flash 1 flash
Off 12.1.1
Press & hold button
Press & release button
Press & release button
Red LEDYellow LED
SounderSee 12.1Replace Alarm
Fault Conditions
ActionRed LEDYellow LED
SounderSee 12.2Replace Alarm
Replace Alarm
Replace Alarm
Replace Alarm
Replace Alarm
Replace Alarm
Low battery 1 flash every 32 seconds
2 flashes every 32 seconds
Off
12.2.1
Clear low battery faultOff
Off for 12 hoursOff for 12 hours
Off for 12 hours
See note *
Press & release button
Contaminated chamber Off
12.2.2
Silence sounding alarm 1 flash every 8 seconds
Off for 10 minutes
Off
Press & release button
within 4 minutes
Silence sounding alarm
(2nd time)
1 flash every 8 seconds
Off for an additional
10 minutes
Off
Press & release button
within 4 minutes
Silence sounding alarm
(3rd time)
2 flashes every 8 seconds
2 rapid beeps every
10 minuites for 8 hours
Off
Standby OffOff
Off
Off 12.1.2
Weekly button test Rapid flashing (0.5 sec)
Rapid flashing (0.5 sec)
Rapid flashing (0.5 sec)
Ramps to full sound 12.1.3 If test fails
If test fails
*Note: We recommend to vacuum the alarm initially (incase of cobwebs etc) and allow 5 minutes before retest, if it still shows a problem , then replace.
Sensing Fire
Full sound
Off
12.1.4
Off
Fire signal from interconnect
Full sound
Full sound
Press & release button
Faulty smoke chamber Off
Off
12.2.3
Silence beeps Off
2 beeps with flashes
1 beep with flash
Off
12.1.6
1 flash every 8 seconds
for 10 minutes
Silence False / Nuisance Alarm
Alarm Silence
Off
12.1.5
Diagnostics Modes
ActionRed LEDYellow LED
SounderSee 12.3Replace Alarm
Replace Alarm
Replace Alarm
Replace Alarm
Predictive failures
12.3.1
Press & hold button
Press & hold button
Press & hold button
Low battery Off
Ramps to full sound
Ramps to full sound
Ramps to full sound
See note
Rapid flash (0.5 sec)
Rapid flash (0.5 sec)
Contaminated chamber Rapid flash (0.5 sec)
alternates with yellow
Rapid flash (0.5 sec)
alternates with yellow
Rapid flash (0.5 sec)
alternates with red
Rapid flash (0.5 sec)
alternates with red
Recommended
Press & hold button
End of Life Test
Off
Alarm memory
12.3.2
24 hour memory
2 flashes every 16 seconds
OffOff
Long term memory Off Rapid chirping
Press & hold button
Press & hold button
Rapid flash (0.5 sec)
Rapid flash (0.5 sec)
Identifying beeping units
12.3.3
Low battery beep Off
Faulty smoke chamber OffOff