eKM Metering Inc.
EKM Metering Inc. – www.ekmmetering.com – info@ekmmetering.com – (831)425-7371
• Nominal Voltage Ranges:
120V to 480V, 2-wire, Single-phase, One Line & Neutral
120V to 480V, 3-wire, Single-phase, 2 Lines & Neutral
120V to 415V, 3-wire, 3-phase, 3 Lines, No Neutral
120V to 480V, 4-wire, 3-phase, 3 Lines and Neutral
• Range of allowable environmental conditions: Pollution Degree 2,
Measurement Category III, Altitude rating 2000 meters max. Maximum
Temperature Range: -30 Deg. C to 70 Deg. C. Tamper Detection Class 1.
The equipment is protected throughout by
double insulation as indicated by this symbol:
• Accuracy Class 0.5
• Rated Frequency: 50Hz/60Hz
• Red LED on the meter face ashes 800 times/kWh. 1 ash = 1.25Wh.
• Received California Type Approval for revenue grade metering
Safety Precautions:
• Meter should be installed by a qualied electrician.
Turn off all power supplying the equipment before preforming any
wiring. Use a properly rated volt meter to conrm power is off.
• Use of this device inconsistent with this manual can cause permanent
damage to the unit and/or serious harm to the operator.
Tools/Materials List:
Volt meter
• Small standard screwdriver
Wire stripper
• DIN-Rail
•16-22 AWG stranded copper wire
• Inline fuse holder with maximum 1Amp fuse
• Use a Type 4 Enclosure (with appropriate conduit and ttings) if meter
will be installed outdoors
Installation Instructions
For All Systems:
1. Disconnect or switch power off before attempting to install, connect,
disconnect or service the meter or the external current transformers
(CTs). ALL POWER MUST BE DISCONNECTED!
2. Mount the meter using 35mm DIN Rail in a protected indoor location.
If installing outdoors, a UL Listed Type 4 Enclosure is required.
3. IMPORTANT: Distinguish and then identify the Neutral and the Line(s)
(‘hot’ wire(s), usually black or red). Label the Neutral and then,
depending on your electrical system, assign labels as described below.
4. Tightening torque of terminals:
All terminals: 4.4 in-lb. (0.5 Nm)
120V, 2-Wire, Single Phase:
1. Label Line 1 as L1.
2. Fit CT1 around L1. Make sure the arrow is facing towards the load (in
the direction of ow). (Fig 2)
3. Black CT wire connects to Port 1 on the Omnimeter. White CT wire
connects to Port 2. (Fig 2)
4. With split core CTs, close the CT around the wire to be measured and
press rmly until you feel and hear it click to indicate full closure. The
buttons should be fully out. Use a zip tieto ensure the CTs remain
securely closed.
5. To power the meter and get a voltage reference: Use a maximum 1.0
Amp inline fuse on L1. Connect one fuse holder pigtail to the breaker,
lug or an appropriate line-tap device, and connect the other pigtail to
16-22 AWG UL rated stranded copper wire for connection to the meter.
6. L1 connects to Port 7 on the Omnimeter, Neutral to Port 10. (Fig 2)
7. Once the meter is properly mounted to the DIN Rail or enclosure and
all wiring is completed, with terminal block covers installed, power can
be turned back on.
8. Meter will then begin cycling through meter values. For details go to:
http://documents.ekmmetering.com/EKM_Metering_LCD_Display_Value_Reading.pdf
9. A video of proper install of a 120V system can be found here:
http://www.youtube.com/watch?v=ky9sgr1LTMk
120/240V, 120/208V, Single Phase, 3-Wire:
1. Label L1 and L2. (Arbitrarily assign labels.)
2. You will be using 2 CTs for this install. Label them CT1 and CT2.
3. Fit CT1 around L1. Make sure the arrow is facing towards the load (in
the direction of ow).
4. Fit CT2 around L2.
(Fig 1)
(Fig 2)
EKM-Omnimeter I v.3 Spec Sheet
1 2 3 4 5 6 7 8 9 10
L1
L2/N
CT1
1 1
1
78
100
.
66.5
Load
current
Basic error %
Class 0.5
Class 1
0.05
I
b
1.0
1.0
1.0
+
0.5
+
1.0
+
1.0
+
0.5
+
0.5
+
1.5
+
1.0
+
1.5
+
1.5
+
1.0
+
1.0
+
0.5(L)
0.8(C)
0.5(L)
0.8(C)
0.1
I
b~
Imax
0.1
I
b
0.2
I
b~
Imax
Power
factor
COSθ
120V, 240V
Single-Phase
2-Wire
Load
Blk Wht
Fuse
Question and Answer IconNeed help?

Do you have a question about the EKM Omnimeter I and is the answer not in the manual?

EKM Omnimeter I Specifications

General IconGeneral
BrandEKM
ModelOmnimeter I
CategoryMeasuring Instruments
LanguageEnglish

Summary

Product Specifications and Safety

Nominal Voltage Ranges

Specifies the allowable voltage ranges for single-phase and three-phase systems.

Safety Precautions

Essential safety guidelines for meter installation and handling by qualified electricians.

Terminal Torque Specification

Details the required tightening torque for all meter terminals.

Single-Phase Installation Instructions

120V, 2-Wire, Single Phase Installation

Step-by-step guide for installing the meter on a 120V single-phase, two-wire system.

120V, 240V, 120/208V, Single Phase, 3-Wire Installation

Instructions for installing the meter on 120/208V and 120/240V single-phase, three-wire systems.

Three-Phase Installation Instructions

120V-415V, 3-Phase, 3-Wire Installation

Procedure for installing the meter on a 120V-415V, three-phase, three-wire system.

120V-480V, 3-Phase, 4-Wire Installation

Guide for installing the meter on a 120V-480V, three-phase, four-wire system.

Meter Functionality and Data

RS-485 and Pulse Output

Details on communication ports, pulse output rate, and LED indicators.

Working Principle and Data Display

Explains meter operation, energy measurement, and the 15 types of data displayed on the LCD.

Handling and Warranty Information

Transport and Handling Guidelines

Recommendations for careful handling, storage, and environmental conditions.

Product Warranty

Information on the two-year warranty and conditions for repair or replacement.