Installaon
21
EN
Air/Flue gas system
FLUE GAS DATA
Boiler
type
Nominal heat
output
Nominal heat
input
Flue
gas
connecon
CO
2
Level
Flue gas
temperature
Flue gas
quanty
Max
permissible
ue
resistance
TRIGON
XL
kW kW mm % °C g/s Pa
max min max min max min max min max min max min
150 142.3 31.3 145.0 32.2 150 ± 1
10.2
± 0.2
9.4
± 0.2
75
± 2
60
± 2
53.7 12.8 200 10
200 190.4 42.0 194.0 43.1 150 ± 1 71.9 17.1 200 10
250 237.6 47.0 242.0 48.4 200 ± 1 89.6 19.2 200 10
300 285.7 56.5 291.0 58.2 200 ± 1 107.8 23.0 160 10
400 381.3 79.6 388.0 80.5 250 ± 1 143.7 30.7 400 10
500 476.7 94.6 485.0 97.0 250 ± 1 179.7 38.4 300 10
570 540.2 120.0 550.0 122.2 250 ± 1 203.7 48.4 480 10
115 113.7 31.3 115.8 32.2 150 ± 1 53.7 12.8 200 10
350 343.5 75.2 349.0 77.6 250 ± 1 143.7 30.7 400 10
The above table shows the maximum permissible ue resistance were the boiler is sll working within specicaons.
Nominal heat input -5%.
Requirements and regulaons
Regulaons for the construcon of ue
gas systems are very dierent for each
country. It should be ensured that all
naonal regulaons with regard to ue
gas systems are respected.
Pay aenon to the following recom-
mendaons when dimensioning a ue
gas system.
Only approved ue gas material may
be used.
The ue gas system must be properly
calculated to ensure a safe funconing
of the system.
Flue gas system components should be
removable for maintenance purposes.
The installer is responsible to apply the
correct diameter, length and type of
ue gas system. If any quesons arise
during the calculaon contact your lo-
cal manufacturer oce for more infor-
maon.