Copyright 2015 ELECTROLUX HOME PRODUCTS PTY LTD Technical Services
ELECTROLUX HOME PRODUCTS PTY LTD
ABN 51 004 762 341
KELVINATOR
SPLIT SYSTEM
AIR-CONDITIONER
MODELS:
KSV53HRA
KSV62HRA
KSV70HRA
Issue: 7
Technical Publication Nº KSSSI90 Date: 12/15
DIAGNOSTIC MANUAL

Table of Contents

Question and Answer IconNeed help?

Do you have a question about the Electrolux KELVINATOR KSV53HRA and is the answer not in the manual?

Electrolux KELVINATOR KSV53HRA Specifications

General IconGeneral
BrandElectrolux
ModelKELVINATOR KSV53HRA
CategoryAir Conditioner
LanguageEnglish

Summary

Not Operating Troubleshooting

Forced Operation Button Troubleshooting

Test unit operation using forced operation button for troubleshooting.

Standby Light Indicator Analysis

Check standby light status for diagnostics on display PCB assembly.

Memory Module PCB Fault Identification

Identify potential fault with the Memory Module PCB for troubleshooting.

Indoor-Outdoor Wiring Configuration Check

Verify indoor-outdoor unit wiring configuration against diagram for correct operation.

Indoor PCB Transformer Voltage Test

Check supply voltage to the transformer on the indoor PCB.

E0 Error

E0 Error: Main Indoor PCB Fault

E0 indicates software/program chip fault on the main indoor PCB assembly.

E1 Error

E1 Error: Communication Protection Diagnosis

Diagnose E1 fault related to indoor/outdoor unit communication protection.

E1 Error: Indoor Unit Component Checks

Perform indoor unit checks, including fan capacitor and motor resistance.

E1 Error: Outdoor Bridge Rectifier Continuity

Test continuity of the outdoor unit's Bridge Rectifier for E1 fault.

E1 Error: Outdoor IGBT Continuity Test

Test continuity of the outdoor unit's IGBT for E1 fault.

E1 Error: Communication Wiring & Earth Checks

Check continuity of the "S" communication wire and Earth connections.

E1 Error: Active/Neutral Wiring Continuity Check

Verify continuity of active and neutral wiring points on outdoor PCB.

E1 Error: 50uf Capacitor to CN3 Continuity

Check continuity of red wire from 50uf capacitor to CN3 on outdoor PCB.

E1 Error: Reactor & PCB Connection Verification

Check continuity from reactor to CN1 and N-B points on outdoor PCB.

E1 Error: Reactor & Relay Continuity Test

Check continuity of reactor (R1502) and connection points to relay.

E1 Error: Outdoor LED Indicator Patterns

Understand outdoor LED light code sequence for E1 fault.

E5 Error

E5 Error: Condenser & Compressor Sensor Checks

Check condenser coil & compressor discharge sensors for connection and continuity.

E52 Error

E52 Error: Condenser Air Sensor Check

Check condenser coil air temperature sensor for connection and continuity.

E6 Error

E6 Error: Indoor Temperature Sensor Checks

Check indoor temperature sensors for connection and continuity.

L2 & PA Error

L2 & PA Error: Condenser Fan Resistance

Measure resistance values of the condenser fan motor plug.

L2 & PA Error: Outdoor PCB Voltage Points

Check AC voltage points on the outdoor main PCB for L2/PA error.

P0 Error

P0 Error: Compressor Terminal Termination

Check compressor run and start terminals for correct termination.

P0 Error: Compressor Resistance & LED Status

Measure compressor winding resistance and check LED configuration.

P1 Error

P1 Error: Voltage Supply & AC Checks

Check supply voltage and AC voltage at CN4/CN5 points for P1 error.

P2 Error

P2 Error: Compressor Wiring & Continuity Test

Check compressor terminals, continuity, and wiring sequence to PCB.

P2 Error: Overload Protector & LED Status

Check overload protector and LED configuration for P2 fault.

P4 Error

P4 Error: Compressor Common Terminal Check

Check compressor common terminal for correct termination.

P4 Error: Compressor Resistance & LED Status

Measure compressor winding resistance and check LED configuration.

P91, LO & E3 Error (KSV26 & 35HRA Only)

P91/LO/E3 Error: Evaporator Fan Resistance

Measure evaporator fan motor plug resistance values for P91/LO/E3 errors.

P91/LO/E3 Error: Indoor PCB Voltage Check

Check AC voltage points on the indoor main PCB for P91/LO/E3 errors.

E3 Error (KSV53HRA Only)

E3 Error: Evaporator Fan & Connector Checks

Check evaporator fan and CN4/CN25 connectors for E3 error.