25-1000-UM 13
2 WRITE DNP3 Object 80 Clear IIN Restart Bit
129 RESPONSE DNP3 Object 1 Variation 1 8 Status points
DNP3 Object 30 Variation 3 - 5 analog values
DNP3 Object 2 Variation 1 - Event Log
Meter Functions
SCS FUNCTION DNP MESSAGE
Get Meter Fault Status CLASS 0 Object 60, Variation 1
Qualifiers: All data. (06H )
APPLICATION FUNCTIONS SUPPORTED: READ
RETURNS: Application Response Function with
STATUS Object 1, Variation 1 and
Object 30 - Variation 3 (as millivolts)
Qualifier: No index packed (00H)
POINTS: 8. See Point description.
Get Meter Event Log, (Changed Status) CLASS 1,2,3 Object 60, Variation 2, 3, or 4
Qualifiers: All data. (06H)
When data is available then in Class 1 data bit is set.
APPLICATION FUNCTIONS SUPPORTED: READ
RETURNS: Application Response Function with
Object 2, Variation 1
Qualifier: 1 octet index, 8 bit quantity (17H)
POINTS: Changed points (10 Max)
if points changed since last read.
If no points changed then an application response is
returned with no object.
(See CLASS 1 point meaning below for Event Log
Description.)
Clear Restart Bit CLASS 80 IIN, Variation 1
Qualifier: No index (0H)
APPLICATION FUNCTIONS SUPPORTED:
WRITE.
RETURNS: Null Response.