7.8 Opening and closing times
The opening and closing times of the barriers are factory-set to standard
values based on the model:
P 2500 = approx. 1.3 seconds
P 3000 = approx. 1.8 seconds
P 3500 = approx. 2.5 seconds
P 4000 = approx. 3.8 seconds
P 5000 = approx. 4.5 seconds
The opening and closing times of the barriers can be changed in the learning
sequence of the controller MO 24 under sequence point P101.
Sequence point P101 = 0 = fast
Sequence point P101 = 1 = standard (factory setting)
Sequence point P101 = 2 = slow
Model-related data P 2500 P 3000 P 3500 P 4000 P 5000
Running time –slow [s] approx.
1.8
approx.
2.5
approx.
3.8
approx.
4.5
approx.
5.5
Running time –standard [s] approx.
1.3
approx.
1.8
approx.
2.5
approx.
3.8
approx.
4.5
Running time – fast [s] approx.
0.9
approx.
1.3
approx.
1.8
approx.
2.8
approx.
3.8
Table 7