1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx iProCHILL 126/205
ES 5
Start of working time band 3 (0-24)
0
24.00
Hr
10 Min
ES 6
End of working time band 3 (0-24)
0
24.00
Hr
10 Min
ES 7
Monday energy saving time band
0 = None
1 = Time Band 1
2 = Time Band 2
3 = Time Bands 1 and 2
4 = Time Band 3
5 = Time Bands 1 and 3
6 = Time Bands 2 and 3
7 = All time bands
0
7
ES 8
Tuesday energy saving time band
0
7
ES 9
Wednesday energy saving time band
0
7
ES 10
Thursday energy saving time band
0
7
ES 11
Friday energy saving time band
0
7
ES 12
Saturday energy saving time band
0
7
ES 13
Sunday energy saving time band
0
7
ES 14
Increase energy saving setting in chiller mode
-50.0
-58
110
230
°C
°F
Dec
int
ES 15
Energy saving differential in chiller mode
0.1
1
25.0
45
°C
°F
Dec
int
ES 16
Energy saving setting increase in heat pump mode
-50.0
-58
110
230
°C
°F
Dec
int
ES 17
Energy saving differential increase in heat pump mode
0.1
1
25.0
45
°C
°F
Dec
int
ES 18
Monday automatic shutdown time band
0
7
ES 19
Tuesday automatic shutdown time band
0
7
ES 20
Wednesday automatic shutdown time band
0
7
ES 21
Thursday automatic shutdown time band
0
7
ES 22
Friday automatic shutdown time band
0
7
ES 23
Saturday automatic shutdown time band
0
7
ES 24
Sunday automatic shutdown time band
0
7
ES 25
Maximum unit working time in OFF from RTC if forced ON via a key
0
250
Min
10 Min
Auxiliary heating
Parameter
Description
min
max
um
Resolution
AH 1
Auxiliary heating function
0 = Disabled
1 = enabled with control in integration mode
2 = enabled with control in heating mode
0
2
AH 2
External air set point auxiliary heating activation
-50.0
-58
110
230
°C
°F
Dec
int
AH 3
External air differential auxiliary heating deactivation
0.1
1
25.0
45
°C
°F
Dec
int
AH 4
Auxiliary heating activation delay time
0
250
AH 5
External air set point that deactivates the compressors working in integration
mode
-50.0
110
°C
°F
Dec
int
AH 6
External air differential that activates the compressors in integration mode
0.1
1
25.0
45
°C
°F
Dec
int
AH 7
Off compressors delay time in integration mode
0
250
AH 8
Thermoregulation selection set
0 = uses the set point (ST04) and the differential (ST08) of the HP
1 = uses the set point and the differential of the auxiliary heating function
2 = add the parameters AH9/AH11 to HP set point (ST04) and use the
differentials AH10/AH12
0
2
AH 9
Auxiliary heating set point on / off
-50.0
-58
110
230
°C
°F
Dec
int
AH 10
Band proportional auxiliary heating ON / OFF
0.1
1
25.0
45
°C
°F
Dec
int
AH 11
Auxiliary modulating heating set point
-50.0
-58
110
230
°C
°F
Dec
int
AH 12
Auxiliary modulating heating proportional band
0.1
1
25.0
45
°C
°F
Dec
int
AH 13
Auxiliary heating modulating minimum output value
0
AH14
%
AH 14
Auxiliary heating modulating maximum output value
AH13
100
%
AH 15
Auxiliary Output heating minimum maintaining value of to higher temperatures
modulating the set point
0 = Not enabled
1 = Enabled
0
1
AH 16
Enable the auxiliary heater in defrost
0 = Not enabled
1 = Enabled
0
1