1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx iProCHILL 140/205
Activation of free cooling
0 = Disabled
1 = enabled fan control with condensing priority
2 = enabled fan control priority with free cooling priority
3 = enabled with external free cooling ventilation
4 = enabled in water/water unit
Free cooling mode input/output differential
The FC function is enabled if the external temperature drops at least FC02
below the evaporator inlet water temperature for at least FC03
Free cooling input/output delay
Damper closing/3-way water valve differential/free cooling ON-OFF relay with
temperature control being satisfired
Band regulation steps/ventilation modulating output in free cooling mode
Regulation steps/ventilation modulating output in free cooling mode
0 = 100% on demand
1 = with step/proportional regulation
Anti-freeze prevention setting with unit in free cooling mode
Free cooling anti-freeze alarm prevention differential
Minimum operation speed of the fans in free cooling mode
Maximum operation speed of the fans in free cooling mode
Peak time at maximum speed after switch-on
Circuit 1 - 2 - 3 - 4 1st step split coil setting
Circuit 1 - 2 - 3 - 4 1st step split coil differential
Circuit 1 - 2 - 3 - 4 2nd step split coil setting
Circuit 1 - 2 - 3 - 4 2nd step split coil differential
Delay for valve exchange of the split coils
Outside Set point temperature air for free cooling enable
Condenser water temperature set point for activation free cooling FC
Delayed activation of the water probe condenser FC free cooling
Delay switching on / off valves free cooling
Free cooling differential
Free cooling delay for the end
Delay for the activation of preventing frost free cooling
Free cooling setpoint valve in chillers
Differential valve free cooling in chiller
Free cooling valve regulation minimum percentage
Free cooling valve regulation maximum percentage
Maintaining minimum valve opening
0 = no
1 = yes
Time to force the Free Cooling starting after start-up (0=function disabled)
Set temperature external air to force the Free Cooling status during the start
up
Auxiliary relay 1 operation
0 = not enabled
1 = always enabled with direct action
2 = enabled with direct action only with the unit ON
3 = always enabled with inverse action
4 = enabled with inverse action only with the unit ON