1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx iProCHILL 147/205
Selection of output circuit valve 2 driver 1
0 = Not present
1 = Circuit 1
2 = Circuit 2
3 = Circuit 3
4 = Circuit 4
Selection of output circuit valve 1 driver 2
0 = Not present
1 = Circuit 1
2 = Circuit 2
3 = Circuit 3
4 = Circuit 4
Selection of output circuit valve 2 driver 2
0 = Not present
1 = Circuit 1
2 = Circuit 2
3 = Circuit 3
4 = Circuit 4
Selection of output circuit valve 1 driver 3
0 = Not present
1 = Circuit 1
2 = Circuit 2
3 = Circuit 3
4 = Circuit 4
Selection of output circuit valve 2 driver 3
0 = Not present
1 = Circuit 1
2 = Circuit 2
3 = Circuit 3
4 = Circuit 4
Selection of output circuit valve 1 driver 4
0 = Not present
1 = Circuit 1
2 = Circuit 2
3 = Circuit 3
4 = Circuit 4
Selection of output circuit valve 2 driver 4
0 = Not present
1 = Circuit 1
2 = Circuit 2
3 = Circuit 3
4 = Circuit 4
Number of additional steps to achieve complete closure. When a closing
request is received, the valve starts from the current number of steps and
moves to 0, then closes for the set number of steps
Number of return steps in opening mode after the valve has been closed
completely. These decompress any closing spring inside the valve or to
prevent sealing the circuit
Maximum number of adjusting steps of the valve
Minimum number of adjusting steps of the valve
Maximum current value per phase of the stepper motor
Maximum number of steps per second of the valve
Indicates the number of steps the valve has to move before compressor start-
up.
0 = function is disabled
Sets valve manual operation mode
0= Automatic
1= Manual
Absolute number of steps the valve has to move in manual mode
Low pressure alarm activation delay (LOP)
High pressure alarm activation delay (MOP)
High overheating alarm activation delay
Low overheating alarm activation delay
PID regulation in chiller mode
PID proportional constant in chiller mode
PID integral time in chiller mode
PID derivative constant in chiller mode
Overheating regulation set point during chiller mode
Overheating regulation dead band in chiller mode
High overheating threshold. The alarm status is signaled after the high
overheating alarm activation delay