9. ANALOGUE - DIGITAL INPUTS/OUTPUTS CONFIGURATIONS
On board of the controller, it allows to configure 20 DI, 15 DO, 10 AI and 6 AO in maximum. If more I/O
needed, please use expansion module IPROEX60D. For one IPROEX60D, it can connect with 3 DI, 6 DO, 7
AI and 3 AO. It can has 4 IPROEX60D at most. In addition, 4 electronic thermostatic drivers XEV20D can
provide 16 more AI (4 for each).
Use parameters in group IO to configure analogue-digital inputs/outputs.
DIGITAL INPUTS CONFIGURATION
IO11 IO30: On board DI (1 - 20)
IO75 IO77: 1
st
expansion DI (1 - 3)
IO94 IO96: 2
nd
expansion DI (1 - 3)
IO113 IO115: 3
rd
expansion DI (1 - 3)
IO132 IO134: 4
th
expansion DI (1 - 3)
DIGITAL OUTPUTS CONFIGURATION
IO31 IO45: On board relays (1 - 15)
IO78 IO83: 1
st
expansion relays (1 - 6)
IO97 IO102: 2
nd
expansion relays (1 - 6)
IO116 IO121: 3
rd
expansion relays (1 - 6)
IO135 IO140: 4
th
expansion relays (1 - 6)
ANALOGUE INPUTS CONFIGURATION
IO01 IO10: On board probes (1 - 10)
IO52 IO55: 1
st
XEV20D probes (1 - 4)
IO56 IO59: 2
nd
XEV20D probes (1 - 4)
IO60 IO63: 3
rd
XEV20D probes (1 - 4)
IO64 IO67: 4
th
XEV20D probes (1 - 4)
IO68 IO74: 1
st
expansion probes (1 - 7)
IO87 IO93: 2
nd
expansion probes (1 - 7)
IO106 IO112: 3
rd
expansion probes (1 - 7)
IO125 IO131: 4
th
expansion probes (1 - 7)
ANALOGUE OUTPUTS CONFIGURATION
IO46 IO51: On board AO (1 - 6)
IO84 IO86: 1
st
expansion AO (1 - 3)
IO103 IO105: 2
nd
expansion AO (1 - 3)
IO122 IO124: 3
rd
expansion AO (1 - 3)
IO141 IO143: 4
th
expansion AO (1 - 3)
Note:
For digital inputs/outputs, it is possible to select polarity. In I/O configuration, use prefix o to indicate open
polarity which means the DI/DO is activated when contact is open; use prefix c to indicate close polarity
which means the DI/DO is activated when contact is closed.
For example:
IO11 = o1 - Remote ON/OFF
IO11 = c1 - Remote ON/OFF
They all mean DI01 is configured as “Remote ON/OFF” but with different polarity. And the DI type is 1.
In the paragraphs below, we will use DI type, DO type, AI type and AO type to indicated function
index of all the I/O.
For analogue inputs/outputs, it is also possible to configured as digital inputs/outputs. For example an AI can
assume values from 0 to 66 (if configured as analog) and from 67 (that correspond to o1) to 296 (that
correspond to c115).
Remember that:
AO1, AO2, AO3 and AO4 can be configured only as 0-10V;
AO5 and AO6 can be configured as 0-10V, PWM and 4-20mA;
in the expansions modules, the AO can be configured only as 0-10V.