10. ALARMS
The alarm codes and signals are made up from letters and numbers that identify the different types.
Types of alarm:
Letter A = unit alarm
Letter B = circuit alarm
Letter C = compressor alarm
10.1 PROBE BREAKDOWN
AP1 …AP54 (probe1 alarm -... probe54 alarm)
Pb AL1 ... Pb AL10 (probe1-...probe10 alarm)
Pb1 AL e1 …Pb7 AL e1 (Expansion1 probe1...probe7 alarm)
Pb1 AL e2 …Pb7 AL e2 (Expansion2 probe1...probe7 alarm)
Pb1 AL e3 …Pb7 AL e3 (Expansion3 probe1...probe7 alarm)
Pb1 AL e4 …Pb7 AL e4 (Expansion4 probe1...probe7 alarm)
Pb1 AL V1... Pb4 AL V1 (XEV20D 1 probe1... XEV20D 1 probe4)
Pb1 AL V2... Pb4 AL V2 (XEV20D 2 probe1... XEV20D 2 probe4)
Pb1 AL V3... Pb4 AL V3 (XEV20D 3 probe1... XEV20D 3 probe4)
Pb1 AL V4... Pb4 AL V4 (XEV20D 4 probe1... XEV20D 4 probe4)
Probe is configured and converted value out of range
Probe is not configured or converted value within range
Alarm relay + buzzer activated
It follows its regulation
It follows its regulation
Free-cooling on/off valve
It follows its regulation
It follows its regulation
It follows its regulation
It follows its regulation
It follows its regulation
*With Ar09 = 1 on if at least 1 probe is configured for control
Pump/and water evaporator
and condenser
*It follows/they follow its/their regulation
WARNING:
Symbol “*” means that the component is only forced to switch-off when the broken probe is a regulation
probe. If the alarm comes from a display probe, the unit continues to follow normal regulation.