1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx iProCHILL 172/205
Free-cooling on/off valve
it follows its regulation
Auxiliary relay
It follows/they follow its/their regulation
Idle running valve
It follows its regulation
Supply ventilation
It follows its regulation
Condensation ventilation
If the Par. FA02= 0 fan working mode dependent on the compressor. With
alarm active the fans are forced to maximum speed for 60 seconds before
switching-off
If the Par. FA02= 1 fan working mode independent from the compressor. With
alarm active the fans are forced to maximum speed for 60 seconds and then
follow their regulation
Support/boiler/anti-freeze
It follows its regulation
Pump/and water evaporator
and condenser
It follows its regulation
Affected circuits
compressors
Off
Unaffected circuits
compressors
It follows its regulation
Unaffected circuits pump
down solenoid valve
It follows its regulation
Affected circuits pump
down solenoid valve
off