1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx iProCHILL 200/205
ACF17
one or more pressure probes defined on a XEV20D module which is not
configured by parameters Et09 – Et16
when SP01 <=1 and Et02≠3 or when SP01>=2 and Et02≠4, configured
XEV20D probes as pressure type.
ACF18
If stepless compressor is enabled (SL01≠0):
SL06>=SL07*10
ST11 ≠ 2 (2=neutral zone regulation)
In one circuit, more than one compressor is configured (CF05…CF08>
1)
compressor is configured but relevant relay Compressor 1…4
intermittent valve is not configured (DO type=52…55).
ACF19
Probe selected by Un05 is not configured.
Probe selected by Un10 is not configured.
Alarm relay (DO type=1) + buzzer activated
10.43 FUNCTION NOT AVAILABLE ALARM
AfnA (Function not available alarm)
Incorrect parameter configuration, enabled some function that not available
yet.
Set ST11 >2
Set DP05-DP08 value >0
Set SP02 =6
Set SP12=1
Set CO19-CO34 value >0
If CO12=2 (Star-delta start-up), relay Star-delta relay is no configured
on board, they are configured in expansion IO board.
If SL01≠0(stepless compressor enabled)
o CO09=1/3.
o No relays configured as Compressor 1…4 Unloader 1(DO
type=79,87,95,103)
o Relays (Screw) Compressor 1…4 intermittent valve (DO
type=52-55) are not configured on board, they are configured in
expansion IO board.
o Relays Compressor 1…4 Unloader 2(DO type=80,88,96,104)
are not configured on board, they are configured in expansion IO
board.