1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx iProCHILL 64/205
When unit is ON in heat pump mode, the status in the screen is Heat Mode:
SWITCH THE UNIT ON/OFF IN COOLING MODE FROM THE VISOTOUCH
The configuration should be:
CF04 = 0, (not Motor condensing unit)
CF02 = 1, (chiller only)
SP09 = 0, (from the keyboard)
In the Visotouch, the left button is always visible and the right button is hidden. The left button will be shown
as when SP08 = 0 and shown as when SP08 = 1.
Press this button for 1 second can switch the device status between cooling mode and stand-by.
SWITCH THE UNIT ON/OFF IN HEATING MODE FROM THE VISOTOUCH
The configuration should be:
CF04 = 0, (not Motor condensing unit)
CF02 = 2, (heat pump only)
SP09 = 0, (from the keyboard)
In the Visotouch, the right button is always visible and the left button is hidden. The right button will be shown
as when SP08 = 0 and shown as when SP08 = 1.
Press this button for 1 second can switch the device status between heating mode and stand-by.