6.2 UNIT SWITH ON/OFF BY RTC
6.2.1 Working With Clock Disabling Digital Input
ES 1
Start of working time band 1 (0-24)
0
24.00
Hr
10 Min
ES 2
End of working time band 1 (0-24)
0
24.00
Hr
10 Min
ES 3
Start of working time band 2 (0-24)
0
24.00
Hr
10 Min
ES 4
End of working time band 2 (0-24)
0
24.00
Hr
10 Min
ES 5
Start of working time band 3 (0-24)
0
24.00
Hr
10 Min
ES 6
End of working time band 3 (0-24)
0
24.00
Hr
10 Min
ES18
Monday automatic shutdown time band
0
7
ES19
Tuesday automatic shutdown time band
0
7
ES20
Wednesday automatic shutdown time band
0
7
ES21
Thursday automatic shutdown time band
0
7
ES22
Friday automatic shutdown time band
0
7
ES23
Saturday automatic shutdown time band
0
7
ES24
Sunday automatic shutdown time band
0
7
If the unit is switch off during switch-off time bands, the screen will be:
If a digital input is configured as Digital input working in RTC automatic enabling (time band)/manual
(keyboard) mode (DI type=91) and is active, the working via the internal clock is disabled. Otherwise, if this
digital input is not configured or configured but not active, enables the working via the internal clock.
The unit is forced to switch off within the time band.
Set the time band with Par ES01-ES06, and select weekly time band by Par ES18-ES24. If current time is
inside the setting band, the unit will be shut off automatically, and the Visotouch shows Unit OFF through
clock.
The RTC time band also can be configured from Visotouch.
Enter into the Set time/date/time bands screen from SERVICE menu.