1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx iProCHILL 75/205
Press the button several times to go back to the main screen.
6.7.2 Setpoint Submenu
To set the setpoint of the cooling and/or heating, press button and enter the set-point screen.
Chiller mode:
Heat pump mode:
To modify the setpoint, click the element Cooling or Heating setpoint then press the button:
The element starts to flash.
Increase or decrease the value using the and buttons.
Confirm the modification by pressing the button again.
In this screen it is also possible to verify (but not modify) whether the energy saving mode and dynamic set
are active. If they are active, the Real set may different from the Cooling or Heating set.
Cooling (Heating) set is always the same as par ST01(ST04), the real set represent the set-point value
including the energy saving delta or of the dynamic set, and it is read only (cant be modified).