1592023020 XM660K_XM669K GB r1.0 07.01.2013.doc XM660K - XM669K 8/8
dAH
1.0 Pr2
Differential for temperature
alarm (defrost probe)
[0.1°C ÷ 25.5°C] [1°F ÷ 45°F]
ddA
15 Pr2
Temperature alarm delay
(defrost probe)
0 ÷ 255 (min.)
FLU
150 Pr2
High temperature alarm setting
(fan probe)
FLL ÷ 150.0° or FLL ÷ 302°F
FLL
-55
Pr2
Low temperature alarm setting
(fan probe)
-55,0°C ÷ FLU or -67°F ÷ FLU
FAH
1.0 Pr2
Differential for temperature
alarm (fan probe)
[0.1°C ÷ 25.5°C] [1°F ÷ 45°F]
FAd
15 Pr2
Temperature alarm delay (fan
probe)
0 ÷ 255 (min.)
dAo
1.3 Pr1
Delay of temperature alarm at
start-up
0 ÷ 24.0(144) (hours.10min)
EdA
30
Pr1
Alarm delay at the end of
defrost
0 ÷ 255 min
dot
15 Pr1
Temperature alarm exclusion
after door open
0 ÷ 255 min
Sti
1.3 Pr2 Stop regulation interval
"nu"(0) ÷ 24.0(144)
(hour.10min)
Std
3 Pr2 Stop duration 1 ÷ 255 min
oA7
ALr Pr2
Modulating output configuration
(if CoM=oA7)
CPr(0) - dEF(1) - FAn(2) -
ALr(3) - LiG(4) - AUS(5) -
db(6) - OnF(7)
CoM
Cur
Pr2
Modulating output configuration
CUr(0) - tEn(1) - PM5(2) -
PM6(3) - oA7(4)
Dig
ital
Inputs
i1P
cL Pr1 Digital input 1 polarity OP(0) - CL(1)
i1F
dor Pr1 Digital input 1 configuration
EAL(0) - bAL(1) - PAL(2) -
dor(3) - dEF(4) - AUS(5) -
LiG(6) - OnF(7) - Htr(8) -
FHU(9) - ES(10) - Hdy(11)
d1d
15 Pr1 Digital input 1 activation delay 0 ÷ 255 (min.)
i2P
cL Pr1 Digital input 2 polarity OP(0) - CL(1)
i2F
LiG Pr1 Digital input 2 configuration
EAL(0) - bAL(1) - PAL(2) -
dor(3) - dEF(4) - AUS(5) -
LiG(6) - OnF(7) - Htr(8) -
FHU(9) - ES(10) - Hdy(11)
d2d
5 Pr1 Digital input 2 activation delay 0 ÷ 255 (min.)
nPS
15 Pr1
Number of pressure switch
activation before lock
0 ÷ 15
OdC
F-C Pr1
Compressor and fan status
when open door
no(0) - FAn(1) - CPr(2) - F-
C(3)
rrd
30 Pr1
Outputs restart after door open
alarm
0 ÷ 255 (min.)
Clock
CbP
Y Pr1 Clock presence n(0) – Y(1)
Hur
- - - Pr1 Current hour - - -
Min
- - -
Pr1
Current minutes - - -
dAY
- - - Pr1 Current day Sun(0) - SAt(6)
Hd1
nu Pr1 First weekly day Sun(0) - SAt(6) - nu(7)
Hd2
nu
Pr1
Second weekly day Sun(0) - SAt(6) - nu(7)
Hd3
nu Pr1 Third weekly day Sun(0) - SAt(6) - nu(7)
ILE
0.0 Pr1
Energy saving cycle start during
workdays
0 - 23.5(143) (hours.10min)
dLE
0.0 Pr1
Energy saving cycle length
during workdays
0 ÷ 24.0(144) (hours.10min)
ISE
0.0 Pr1
Energy saving cycle start during
holidays
0 - 23.5(143) (hours.10min)
dSE
0.0 Pr1
Energy saving cycle length
during holidays
0 ÷ 24.0(144) (hours.10min)
HES
0.0 Pr1
Temperature increasing during
Energy Saving cycle
[-30.0°C ÷ 30.0°C] [-54°F ÷
54°F]
Ld1
nu Pr1 Workdays First defrost start
0.0 ÷ 23.5(143) - nu(144)
(hours.10min)
Ld2
nu Pr1 Workdays Second defrost start
Ld1 ÷ 23.5(143) - nu(144)
(hours.10min)
Ld3
nu Pr1 Workdays Third defrost start
Ld2 ÷ 23.5(143) - nu(144)
(hours.10min)
Ld4
nu Pr1 Workdays Fourth defrost start
Ld3 ÷ 23.5(143) - nu(144)
(hours.10min)
Ld5
nu Pr1 Workdays Fifth defrost start
Ld4 ÷ 23.5(143) - nu(144)
(hours.10min)
Ld6
nu Pr1 Workdays Sixth defrost start
Ld5 ÷ 23.5(143) - nu(144)
(hours.10min)
Sd1
nu Pr1 Holidays First defrost start
0.0 ÷ 23.5(143) - nu(144)
(hours.10min)
Sd2
nu Pr1 Holidays Second defrost start
Sd1 ÷ 23.5(143) - nu(144)
(hours.10min)
Sd3
nu Pr1 Holidays Third defrost start
Sd2 ÷ 23.5(143) - nu(144)
(hours.10min)
Sd4
nu Pr1 Holidays Fourth defrost start
Sd3 ÷ 23.5(143) - nu(144)
(hours.10min)
Sd5
nu Pr1 Holidays Fifth defrost start
Sd4 ÷ 23.5(143) - nu(144)
(hours.10min)
Sd6
nu Pr1 Holidays Sixth defrost start
Sd5 ÷ 23.5(143) - nu(144)
(hours.10min)
Energy Saving
ESP
P1 Pr1 Energy saving probe selection
nP(0) - P1(1) - P2(2) - P3(3) -
P4(4) - P5(5) - tEr(6)
HES
0.0 Pr1
Temperature increasing during
Energy Saving
[-30.0°C ÷ 30.0°C] [-54°F ÷
54°F]
PEL
n Pr1
Energy saving activation when
Light switched off
n(0) – Y(1)
L.A.N. Management
LMd
y Pr2 Defrost Synchronisation n(0) – Y(1)
dEM
y Pr2 Defrost end Synchronisation n(0) – Y(1)
LSP
n Pr2 SET-POINT Synchronisation n(0) – Y(1)
LdS
n Pr2
Display Synchronisation
(temperature sent via LAN)
n(0) – Y(1)
LOF
n Pr2 ON/OFF Synchronisation n(0) – Y(1)
LLi
y Pr2 Light Synchronisation n(0) – Y(1)
LES
n Pr2 Energy Saving Synchronisation n(0) – Y(1)
LSd
n Pr2 Remote probe displaying n(0) – Y(1)
LPP
n Pr2 Pressure value sent in LAN n(0) – Y(1)
StM
n Pr2
Cooling request from LAN
enable compressor relay
n(0) – Y(1)
Probe Configurations
P1C
NtC Pr2 P1 configuration nP(0) - Ptc(1) - ntc(2) - PtM(3)
ot
0.0 Pr2 P1 calibration
[-12,0°C ÷ 12,0°C] [-21°F ÷
21°F]
P2C
NtC
Pr2
P2 configuration nP(0) - Ptc(1) - ntc(2) - PtM(3)
oE
0.0 Pr2 P2 calibration
[-12,0°C ÷ 12,0°C] [-21°F ÷
21°F]
P3C
NtC Pr2 P3 configuration nP(0) - Ptc(1) - ntc(2) - PtM(3)
o3
0.0 Pr2 P3 calibration
[-12,0°C ÷ 12,0°C] [-21°F ÷
21°F]
P4C
NtC Pr2 P4 configuration nP(0) - Ptc(1) - ntc(2) - PtM(3)
o4
0.0 Pr2 P4 calibration
[-12,0°C ÷ 12,0°C] [-21°F ÷
21°F]
P5C
420 Pr2 P5 configuration
nP(0) - Ptc(1) - ntc(2) - PtM(3)
- 420(4) - 5Vr(5)
o5
0.0
Pr2
P5 calibration
[-12,0°C ÷ 12,0°C] [-21°F ÷
21°F]
P6C
PtM Pr2 P6 configuration nP(0) - Ptc(1) - ntc(2) - PtM(3)
o6
0.0 Pr2 P6 calibration
[-12,0°C ÷ 12,0°C] [-21°F ÷
21°F]
Service
CLt
- - - Pr1 ON/OFF percentage (C.R.O.) (read only)
tMd
- - - Pr1
Time remaining before next
defrost activation (only for
interval defrost)
(read only)
LSn
- - - Pr1 Number of devices in LAN 1 ÷ 8 (read only)
LAn
- - - Pr1 List of address of LAN devices 1 ÷ 247 (read only)
Other
Adr
1
Pr1
Modbus address 1 ÷ 247
rEL
- - - Pr1 Firmware release (read only)
Ptb
- - - Pr1 Parameter table (read only)
Pr2
- - -
Pr1
PR2 menu access (read only)