EasyManua.ls Logo

Emerson DIXELL XR30CHC

Emerson DIXELL XR30CHC
6 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1592034030 XR30CHC EN r1.0 2019.01.31 XR30CHC 3/6
LS
Minimum Set Point: (-100.0°C to SET; -148°F to SET) sets the minimum value for the set
point.
US
Maximum Set Point: (SET to 200.0°C; SET to 392°F) set the maximum value for set point.
HY
Differential in normal mode: (0.1 to 25.0°C; 1 to 45°F) differential for set point. Compressor
Cut-IN is T > SET + HY. Compressor Cut-OUT is T<=SET.
HYE
Differential in energy saving mode: (0.1 to 25.0°C; 1 to 45°F) differential for set point.
Compressor Cut-IN is T > SET + HES + HYE. Compressor Cut-OUT is T<= SET + HES.
odS
Outputs delay activation after power on: (0 to 255 min) this function is enabled after the
power-on of the instrument and delays output activations.
AC
Anti-short cycle delay: (0 to 50 min) minimum interval between a compressor stop and the
following restart.
rtr
Percentage for regulation: 100=P1 only; 0=P2 only
CCt
Maximum duration for pull down: (0.0 to 23h50min, res. 10min) after elapsing this interval of
time the super cooling function is immediately stopped
CCS
Differential for pull down: (-12.0 to 12.0°C; -21 to 21°F) during any super cooling phase the
regulation SETPOINT is moved to SET+CCS (in normal mode) or to SET+HES+CCS (in
energy saving mode)
oHt
Overheating before activating the pull-down function (when in normal mode): (1.0 to
12.0°C; 1 to 21°F) this is the upper threshold limit used to activate the super cooling function.
oHE
Overheating before activating the pull-down function (when in energy saving mode): (1.0
to 12.0°C; 1 to 21°F) this is the upper threshold limit used to activate the super cooling
function.
Con
Compressor ON time with faulty probe: (0 to 255 min) time during which the compressor is
active in case of faulty thermostat probe. With CY=0 compressor is always OFF.
CoF
Compressor OFF time with faulty probe: (0 to 255 min) time during which the compressor is
OFF in case of faulty thermostat probe. With Cn=0 compressor is always active.
PROBE SETUP - Prb
PbC
Probe selection: ntC; PtC; Pt1000
ot
Probe P1 calibration: (-12.0 to 12.0°C; -21 to 21°F) allows to adjust any possible offset of the
first probe.
P2P
Evaporator probe presence: n = not present; Y = the defrost stops by temperature.
oE
Evaporator probe calibration: -12.0 to 12.0°C; -21 to 21°F) allows to adjust any possible
offset of the third probe.
P3P
Third probe presence: n = not present; Y = the defrost stops by temperature.
o3
Third probe calibration: -12.0 to 12.0°C; -21 to 21°F) allows to adjust any possible offset of
the third probe.
DISPLAY - diS
iCo
Enabling icon visualisation: (n; Y) the icons can be hidden during normal functioning
CF
Temperature measurement unit: (°C; °F) °C = Celsius; °F = Fahrenheit.
rES
Resolution (only for °C): (dE; in) dE = decimal; in = integer.
Lod
Probe displayed: (P1; P2; P3; P4; SEt; dtr; USr) Px=probe “x”; SEt=set point; dtr=do not
use it; USr=do not use it.
dLY
Temperature visualization delay: (0.0 to 20min00sec, res. 10 sec) when the temperature
increases, the display is updated of 1°C or 1°F after this time.
dtr
Visualization percentage = F(P1;P2): (0 to 100) with dtr=1 the display will show this value
VALUE=0.01*P1+0.99*P2
DEFROST - dEF
idF
Interval between two consecutive defrost cycles: (0 to 255 hours) determines the time
interval between the beginnings of two defrosting cycles.
MdF
Maximum length for defrost: (0 to 255 min; 0 means no defrost) when P2P=n (no evaporator
probe presence) it sets the defrost duration, when P2P=Y (defrost end based on evaporator
temperature) it sets the maximum length for defrost.
dSd
Start defrost delay: (0 to 255 min) delay in defrost activation.
dFd
Display during defrost: (rt; it; SP; dF) rt = real temperature; it = start defrost temperature;
SP = SET-POINT; dF = label “dF”.
dAd
Max delay for updating display after any defrost: (0 to 255 min) delay before updating the
temperature on the display after finishing any defrost.
Fdt
Draining time: (0 to 255 min)
dPo
First defrost after start-up: (n; Y) to enable defrost at power on.
dAF
Defrost delay after freezing: (0.0 to 24h00min, res. 10 min) delay before activating a defrost.
od1
Automatic defrost (at the beginning of any energy saving mode): (n; Y) n=function
disabled; Y=function enabled
FAN - FAn
FAC
Probe selection for condenser fan management: nP=no probe; P1=probe Pb1; P2=probe
Pb2; P3=probe Pb3; P4=probe Pb4 on Hot Key plug.
St2
Condenser fan stop temperature: (-55 to 50°C; -67 to 122°F) setting of temperature,
detected by evaporator probe. Over this value of temperature fans are always OFF.
HY2
Differential for condenser fan: (0.1 to 25.5°C; 1 to 45°F) differential for evaporator ventilator
regulator
FCC
Condenser fan mode operation: (Cn; on; CY; oY)
Cn = runs with the compressor and OFF during defrost
on = continuous mode, OFF during defrost
CY = runs with the compressor and ON during defrost
oY = continuous mode, ON during defrost
ALARMS - ALr
ALP
Temperature alarms probe selection: (P1, P2, P3, P4)
ALC
Temperature alarms configuration: (Ab, rE) Ab = absolute; rE = relative.
ALU
Maximum temperature alarm: when this temperature is reached, the alarm is enabled after
the Ad delay time.
If ALC=Ab ALL to 150.0°C or ALL to 302°F.
If ALC=rE 0.0 to 50.0°C or 0 to 90°F.
ALL
Minimum temperature alarm: when this temperature is reached, the alarm is enabled after the
Ad delay time.
If ALC=Ab -55.0°C to ALU or -67°F to ALU.
If ALC=rE 0.0 to 50.0°C or 0 to 90°F.
AFH
Differential for temperature alarm recovery: (0.1 to 25.0°C; 1 to 45°F) differential for alarms.
ALd
Temperature alarm delay: (0 to 255 min) delay time between the detection of an alarm
condition and the relative alarm signalling.
dot
Delay of temperature alarm with door open: (0.0 to 24h00min, res. 10 min) delay time
between the detection of a temperature alarm condition and the relative alarm signalling, after
powering on the instrument.
dAo
Delay of temperature alarm at start up: (0.0 to 24h00min, res. 10 min) delay time between
the detection of a temperature alarm condition and the relative alarm signalling, after powering
on the instrument.
CONDENSER TEMPERATURE ALARM - ALr
AP2
Probe selection for second temperature alarms: (nP; P1; P2; P3; P4) nP=no probe;
P1=thermostat probe; P2=evaporator probe; P3=do not use it; P4=Probe on Hot Key plug
AU1
Second high temperature pre-alarm: (-55.0 to 150.0°C; -67 to 302°F)
AH1
Differential for second temperature pre-alarm recovery: (0.1 to 25.0°C; 1 to 45°F)
Ad1
Second temperature pre-alarm delay: (0 to 255 min; 255 = not used) delay time between the
detection of a condenser pre-alarm condition and the relative alarm signaling.
AL2
Second low temperature alarm: (-55.0 to 150.0°C; -67 to 302°F)
AU2
Second high temperature alarm: (-55.0 to 150.0°C; -67 to 302°F)
AH2
Differential for second temperature alarm recovery: (0.1 to 25.0°C; 1 to 45°F)
Ad2
Second temperature alarm delay: (0 to 255 min; 255 = not used) delay time between the
detection of a condenser alarm condition and the relative alarm signaling.
dA2
Delay for second temperature alarm at start up: (0.0 to 24h00min, res. 10 min)
bLL
Compressor off because of second low temperature alarm: (n; Y) n = no, compressor
keeps on working; Y = yes, compressor is switched off till the alarm is present, in any case
regulation restarts after AC time at minimum.
AC2
Compressor off because of second high temperature alarm: (n; Y) n = no, compressor
keeps on working; Y = yes, compressor is switched off till the alarm is present, in any case
regulation restarts after AC time at minimum.
SAF
Differential for anti freezing control: (-12.0 to 12.0°C; -21.0 to 21.0°F) regulation sopped if
T<SET+SAF
DIGITAL OUTPUT MANAGEMENT - oUt
tbA
Alarm muting: (n; Y) to disable the (optional) buzzer and the output configured as alarm.
oAx
(x=1,2)
Output configuration: (nu; CP1; dEF; FAn; ALr; LiG; AUS; db; onF; HES; Cnd) nu=not
used; CP1=compressor; dEF=defrost; FAn=ventilators; ALr=alarm; LiG=light;
AUS=Auxiliary relay; onF=always on with instrument on; db=neutral zone; HES=night blinds;
Cnd=Condenser fan; CP2=second compressor; dF2=second defrost; HEt=heater control;
inV=do not use it.
AoP
Alarm relay polarity: (oP; CL) oP = alarm activated by closing the contact; CL = alarm
activated by opening the contact
DIGITAL INPUT - inP
ibt
Base time for digital inputs: (SEC; Min) SEC = seconds; Min = minutes. Delay for activating
the function linked to the digital inputs.
i1P
Digital input 1 polarity: (oP; CL) oP = activated by closing the contact; CL = activated by
opening the contact.
i1F
Digital input 1 configuration: (nu; dor; dEF; AUS; ES; EAL; bAL; PAL; FAn; HdF; onF; LiG;
CC; EMt)
nu=not used
dor = door switch function
dEF = defrost activation
AUS = auxiliary output
ES = energy saving mode activation
EAL = external warning alarm
bAL = external lock alarm
PAL = external pressure alarm
FAn = evaporator fan control
HdF = holiday defrost
onF = ON/OFF status change
LiG = light output control
CC = change configuration (between C1 and C2)
EMt = do not use it
did
Digital inputs 1 alarm delay: (0 to 255) it is the delay between the detection of an external
event and the activation of the relative function.
i2P
Digital input 2 polarity (if d.i.2 present): (oP; CL) oP = activated by closing the contact; CL =
activated by opening the contact.
i2F
Digital input 2 configuration: (nu; dor; dEF; AUS; ES; EAL; bAL; PAL; FAn; HdF; onF; LiG;
CC; EMt)
nu=not used
dor = door switch function
dEF = defrost activation
AUS = auxiliary output
ES = energy saving mode activation
EAL = external warning alarm
bAL = external lock alarm
PAL = external pressure alarm
FAn = evaporator fan control
HdF = holiday defrost
onF = ON/OFF status change
LiG = light output control
CC = change configuration (between C1 and C2)
EMt = Motion detector
d2d
Digital inputs 2 alarm delay: (0 to 255) it is the delay between the detection of an external
event and the activation of the relative function.
nPS
Number of external pressure alarms before stopping the regulation: (0 to 15) after
reaching nPS events in the digital input alarm delay (par. dxd) the regulation will be stopped
and a manual restart (ON/OFF, power OFF and power ON) will be required
odC
Compressor and fan status after door opening: (no; FAn; CPr; F-C): no = normal;
FAn = Fans OFF; CPr = Compressor OFF; F-C = Compressor and fans OFF.
rrd
Regulation restart after door open alarm: (n; Y) n = no regulation if door is opened; Y = when
did is elapsed, regulation restarts even if a door open alarm is present.
LCi
Light output controlled by digital input: (0 to 255 min) a digital input event will activate the
light output and the output will stay ON for this interval
ENERGY SAVING - ES
HES
Differential for energy saving mode: (-30.0 to 30.0°C; -54 to 54°F) it sets the increasing
value of the set point during the Energy Saving cycle.

Related product manuals