Identifier VM_DC_VOLTAGE_SET
Description Range applied to d.c. voltage reference parameters
Units V
Range of [MIN] 0
Range of [MAX] 0.0 to 1150.0
VM_DC_VOLTAGE_SET[MAX] is drive voltage rating dependent. All values are shown in the table below.
Voltage level 200V 400V 575V 690V
VM_DC_VOLTAGE_SET[MAX] 400 800 955 1150
VM_DC_VOLTAGE_SET[MIN] = 0
Identifier VM_DRIVE_CURRENT
Description Range applied to parameters showing current in A
Units A
Range of [MIN] -99999.999 to 0.000
Range of [MAX] 0.000 to 99999.999
VM_DRIVE_CURRENT[MAX] is equivalent to the full scale (over current trip level) for the drive and is given by Full Scale Current Kc (11.061).
VM_DRIVE_CURRENT[MIN] = - VM_DRIVE_CURRENT[MAX]
Identifier VM_DRIVE_CURRENT_UNIPOLAR
Description Unipolar version of VM_DRIVE_CURRENT
Units A
Range of [MIN] 0.000
Range of [MAX] 0.000 to 99999.999
VM_DRIVE_CURRENT_UNIPOLAR[MAX] = VM_DRIVE_CURRENT[MAX]
VM_DRIVE_CURRENT_UNIPOLAR[MIN] = 0.000
Identifier VM_HIGH_DC_VOLTAGE
Description Range applied to the parameters showing high d.c. voltage
Units V
Range of [MIN] 0
Range of [MAX] 0 to 1500
VM_HIGH_DC_VOLTAGE[MAX] = 1500. This is the full scale d.c. link voltage feedback for the high d.c. link voltage measurement which can measure
the voltage if it goes above the normal full scale value.
VM_HIGH_DC_VOLTAGE[MIN] = 0
Identifier VM_LOW_UNDER_VOLTS
Description Range applied to the low under voltage threshold
Units V
Range of [MIN] 24
Range of [MAX] 24 to 1150
If Back-up Mode Enable (06.068) = 0
VM_LOW_UNDER_VOLTS[MAX] = VM_STD_UNDER_VOLTS[MIN]
Otherwise
VM_LOW_UNDER_VOLTS[MAX] = VM_STD_UNDER_VOLTS[MIN] / 1.1.
VM_LOW_UNDER_VOLTS[MIN] = 0.
Identifier VM_MIN_SWITCHING_FREQUENCY
Description Range applied to the minimum switching frequency parameter
Units User units
Range of [MIN] 0
Range of [MAX] 0 to 6
VM_MIN_SWITCHING_FREQUENCY[MAX] = Maximum Switching Frequency (05.018)
VM_MIN_SWITCHING_FREQUENCY[MIN] = 0 for motor control modes, or 1 for Regen mode (subject to the maximum)
Powerdrive F300 Parameter Reference Guide
Issue: 01.15.00
13