Parameter 01.029 Skip Reference 1
Short description Defines the 1st reference point to skip
Mode OpenLoop
Minimum 0.0 Maximum 550.0
Default 0.0 Units
Type 16 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 1
Coding RW
The skip references functions are available to prevent continuous operation within a specified speed range (i.e. where mechanical resonance may occur).
When Skip Reference 1 (01.029) = 0 Filter 1 is disabled. Skip Reference Band 1 (01.030) defines the range either side of Skip Reference 1 (01.029) over
which references are rejected in either direction. The actual rejection band is therefore twice that defined by Skip Reference Band 1 (01.030) with
Skip Reference 1 (01.029) as the centre of the band. When the selected reference is within the rejection band the lower limit of the band is passed through
the filter so that reference is always less than demanded.
Filter 2 (Skip Reference 2 (01.031), Skip Reference Band 2 (01.032)) and Filter 3 (Skip Reference 3 (01.033), Skip Reference Band 3 (01.034)) operate in
the same ways as Filter 1.
If any of the filters are active (i.e. the reference is within their rejection band) Reference In Rejection Zone (01.035) is set to 1, otherwise it is 0.
Parameter 01.030 Skip Reference Band 1
Short description Defines the range either side of skip reference 1 to be implemented
Mode OpenLoop
Minimum 0.0 Maximum 25.0
Default 0.0 Units
Type 8 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 1
Coding RW, BU
See Skip Reference 1 (01.029).
Parameter 01.031 Skip Reference 2
Short description Defines the 2nd reference point to skip
Mode OpenLoop
Minimum 0.0 Maximum 550.0
Default 0.0 Units
Type 16 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 1
Coding RW
See Skip Reference 1 (01.029).
Parameter 01.032 Skip Reference Band 2
Short description Defines the range either side of skip reference 2 to be implemented
Mode OpenLoop
Minimum 0.0 Maximum 25.0
Default 0.0 Units
Type 8 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 1
Coding RW, BU
See Skip Reference 1 (01.029).
Parameter 01.033 Skip Reference 3
Short description Defines the 3rdreference point to skip
Mode OpenLoop
Minimum 0.0 Maximum 550.0
Default 0.0 Units
Type 16 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 1
Coding RW
See Skip Reference 1 (01.029).
Parameter 01.034 Skip Reference Band 3
Short description Defines the range either side of skip reference 3 to be implemented
Mode OpenLoop
Minimum 0.0 Maximum 25.0
Default 0.0 Units
Type 8 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 1
Coding RW, BU
28
Powerdrive F300 Parameter Reference Guide
Issue: 01.15.00