Menu 3 Single Line Descriptions − Frequency Monitoring
Mode: OpenLoop
Parameter Range Default Type
03.005 Zero Speed Threshold 0.0 to 20.0 Hz 1.0 Hz RW Num US
03.006 At Speed Lower Limit 0.0 to 550.0 Hz 1.0 Hz RW Num US
03.007 At Speed Upper Limit 0.0 to 550.0 Hz 1.0 Hz RW Num US
03.008 Over Speed Threshold 0.0 to 550.0 Hz 0.0 Hz RW Num US
03.009 Absolute At Speed Select Off (0) or On (1) Off (0) RW Bit US
RW Read / Write RO Read-only Bit Bit parameter Txt Text string Date Date parameter Time Time parameter
Chr Character parameter Bin Binary parameter IP IP address Mac MAC address Ver Version number SMP Slot, menu, parameter
Num Number parameter DE Destination ND
No
default value
RA Rating dependent NC Non-copyable PT Protected
FI Filtered US User save PS
Power-
down save
Powerdrive F300 Parameter Reference Guide