EasyManuals Logo

Emerson QuickPanel+ IC755C S06RD Series Quick Start Guide

Emerson QuickPanel+ IC755C S06RD Series
42 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #35 background imageLoading...
Page #35 background image
Quick Start Guide Section 5
GFK-2893P Sep 2019
Product Certification & Installation Guidelines 35
Description
Agency
Marking
Comments
7, 10, 12, 15” units
only.
5.2 Conditions of Safe Use for
Installation in Hazardous Locations
The following information applies to products bearing
the UL marking for Hazardous areas and the ATEX
marking for Zone 2 explosive atmospheres:
Suitable for use in Class I Division 2 Groups A, B, C,
D; Class 2 Division 2 Groups F, G; Class 3 Division 1
and Division 2.
Suitable for Group II, Category 3, Gas Groups IIC,
Dust Group IIIC (applicable only to the
IC755CSW07CDACA, IC755CSS10CDACA,
IC755CSS12CDBCA, and IC755CSS15CDACA Display
units):
1. The equipment shall only be used in an area of at
least pollution degree 2, as defined in IEC 60664-1.
Note: Pollution degree 2 can be achieved when the
installation is in a controlled environment with suitably
controlled condensation or airborne pollution.
2. The equipment shall be installed in an enclosure
that provides a minimum ingress protection of IP
54 in accordance with IEC 60079-0.

Other manuals for Emerson QuickPanel+ IC755C S06RD Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson QuickPanel+ IC755C S06RD Series and is the answer not in the manual?

Emerson QuickPanel+ IC755C S06RD Series Specifications

General IconGeneral
BrandEmerson
ModelQuickPanel+ IC755C S06RD Series
CategoryMonitor
LanguageEnglish

Related product manuals