EasyManua.ls Logo

Emerson QuickPanel+ IC755C S06RD Series - Page 40

Emerson QuickPanel+ IC755C S06RD Series
42 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Quick Start Guide Section 5
GFK-2893P Sep 2019
Product Certification & Installation Guidelines 40
Industry Canada requires the following note to be
published:
Note: This Class A digital apparatus complies with Canadian
CAN ICES-3 (A)/NMB-3 (A).
5.4 EMC Installation and Operation
Considerations
This equipment is intended for industrial use only and
complies with a minimum level of EMC performance as
defined by EN 61000-6-2 and EN 61000-6-4 standards.
To meet these requirements, the following installation
and operation considerations to be considered:
Shielding USB cables
Limiting RS-232 cables to 15 m (49.2 ft) in
length
Using Audio ports only during operational
maintenance
Although these considerations were deliberated during
testing, actual EMC environments vary greatly.
Therefore, these considerations may not be necessary.
Likewise, additional measures, such as filtering, wire
separation, and cable routing, may need to be
considered to ensure intended operation of the overall
system.

Related product manuals