Product Data Sheet
00813-0100-4530, Rev DA
December 2010
19
Rosemount 5300 Series
FOUNDATION™ fieldbus (Output Option Code F) - (See Ordering Information in Table 1 on page 4 and
Table 2 on page 11)
Output
External Power Supply
(1)
The input voltage for FOUNDATION™ fieldbus is 9-32 Vdc (9-30 Vdc in IS applications, and 16-32 Vdc
in Explosion-proof/Flameproof applications)
The input voltage for FISCO, IS applications is 9-17.5 Vdc
For Flameproof/Explosion-proof installations the Rosemount 5300 Series transmitters have a built-in
barrier; no external barrier needed.
Quiescent Current Draw 21 mA
F
OUNDATION fieldbus Blocks Resource block, 3 Transducer blocks, 6 AI blocks, PID block, ISEL block, SGCR block, ARTH block,
and OS block
F
OUNDATION fieldbus Class (Basic
or Link Master)
Link Master (LAS)
F
OUNDATION fieldbus Block
Execution Time
AI-block: 30 ms. PID-block: 40 ms
ARTH-, ISEL-, OSPL-block: 65 ms. CHAR-block: 75 ms
F
OUNDATION fieldbus Instantiation No
Conforming F
OUNDATION fieldbus ITK 5.0
F
OUNDATION fieldbus PlantWeb
Alert Support
Yes
Host / DCS system (e.g. DeltaV™)
Maintenance
H2 - High Speed
Field Bus
H1 - Low Speed
Field Bus
Field
Communicator
Rosemount 5301
6200 ft (1900 m)
max (depending
upon cable
characteristics)
Rosemount 5401
Rosemount 5601
PC with Rosemount
Radar Master
Fieldbus
Modem
Rosemount 752
Field Signal
Indicator