EasyManua.ls Logo

EMI Corp - Unit Start-Up and Sequence of Operation

EMI Corp
20 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
www.enviromaster.com
14
Multi-zone Heat Pump Condensing Units
STARTING THE UNIT
Before starting the unit in cool weather,
power the system 24 hours before at-
tempting to start.
Do a final system check using the super
-
heat/subcooling method. Record results
on Test Unit Performance Data sheet
(next page).
- Cooling mode superheat is set with a proper
sized piston and charge, using the field
charging charts.
- Heating mode superheat is set with a TXV
and should be 5°F. When charging a system
in heat mode, use the subcool methodeld
charging charts.
FIELD CHARGING
Example (Using the 12,000 Btuh cooling
chart):
1. Suction pressure is 65 psi. which equals
38
° F on The R-22 Scale of the Low-
Side Gauge.
2. Suction line temperature taken at the
unit is 70
° F. 70° F minus 38° F equals
32° F superheat.
3. Outdoor temperature is 90° F; indoor
temperature is 80° F.
4. Intersection of the indoor-temperature
and outdoor-temperature lines occur on
the 12° F superheat line.
5. Add charge to obtain 12° F superheat.
Instructions:
1. Measure suction pressure and determine
evaporator-refrigerant temperature on
R-22 scale of low-side gauge.
2. Measure suction-line temperature on
suction line of the unit.
3. Measure outdoor and indoor tempera-
tures.
4. Determine from the table what the super
-
heat should be for the indoor and outdoor
temperatures. (Example indicates 12
° F
superheat.)
5. Adjust charge if needed. Be sure unit is
running at stabilized condition.
NOTE: If operating superheat is more
than F above the chart value, add
refrigerant. If below the chart value
remove refrigerant. If below the limit
line, remove refrigerant.
REFRIGERANT PIPING INSTALLATION SECTION
NOTE: For installation of the indoor unit
and start-up of the system, please refer
to the appropriate installation manual
for your indoor product to complete the
installation.
Remove gauge set. Mount all access panels
and make sure they are properly secured.
Make final visual inspection and repair
any deficiencies.
(Proceed to the Sequence Of Operation
on the following pages)

Related product manuals