EasyManua.ls Logo

EMI S1C - Page 20

EMI S1C
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
www.enviromaster.com
Side Discharge Condensers
20
SINGLE-ZONE AND DUAL-ZONE SEQUENCE OF OPERATION
Note: For remote wall mounted ther-
mostat operation be sure to select EMI
p/n 240004180 or a suitable 24
V, two
sage heating, heat pump thermostat.
Condenser operation: The transform-
er located in the indoor unit provides 24V,
low-
Volt control power to the condenser
(outdoor unit). This can be measured
across low-
Volt terminals “R” and “C”.
Single zone heat pump condensers
utilize a reversing valve to provide re-
verse cycle operation. Therefore the out
-
door unit will act as either a condenser or
an evaporator there-by providing comfort
cooling or heating to the indoor space.
The reversing valve is energized in cool
-
ing. Should the valve fail to actuate, the
system will default to the heating mode of
operation.
Cooling operation, single-zone and
dual-zone: Cooling operation requires that
the control (either unit mount or remote
wall mount thermostat) make a connec
-
tion between low-
Volt terminals “R” and
“Y” along with “R” and “O” (heat pumps
only). When the indoor control is placed
in cooling mode, with the set point tem
-
perature below the room temperature, the
reversing valve will energize (R & O heat
pumps only) along with the compressor
and outdoor fan (R & Y). When the indoor
control is satisfied and the room tempera-
ture falls below the set temperature, the
compressor and fan will de-energize. The
anti-short cycle timer (ASCT) will prevent
the compressor from re-starting for three
minutes.
Heating operation (heat pumps only):
Heating operation requires that the con
-
trol (either unit mount or remote wall
mount, heat pump thermostat) make a
connection between low-Volt terminals
“R” and “Y” only. When the indoor control
is placed in heating mode, with the set
point temperature above room tempera-
ture, the compressor and outdoor fan
(R & Y) will energize. When the indoor
control is satisfied and the room temper
-
ature rises above the set temperature,
the compressor and fan will de-energize.
The anti-short cycle timer (ASCT) will
prevent the compressor from re-starting
for three minutes.
Defrost controls with short cycle
protection (heat pumps only): The unit
is equipped with a logic control circuit de-
signed to keep system operating at peek
efficiency. The 24
V circuit provides control
to the indoor and outdoor systems includ-
ing a three minute, anti-short cycle timer
(ASCT) compressor protection.
The defrost control circuit is designed
to keep the condenser coil free from frost
and ice during heating mode. This is ac
-
complished through the precise switching
sequence of the outdoor fan, reversing
valve and indoor auxiliary heater.
Defrost initiation: The defrost-sensor
is located on either the end plate or the re-
turn bend of the condenser coil. A defrost
cycle will initiate after the sensor closes
(approx. 30° F) and remains closed for
the length of time selected on the control
board (either 30, 60 or 90 minutes)*.
At the start of the defrost cycle, the re
-
versing valve will change from heating to
cooling mode. The condenser fan will also
switch off there-by allowing pressure and
temperature to rise within the condenser
coil to melting off any ice build-up. At the
same time the unit will switch on the in-
door electric strip heater to temper the
cold air being discharged from the evapo
-
rator unit. This will continue until either
the defrost-sensor opens (approx. 60° F)
or a 10-minute maximum cycle time has
elapsed. Defrost times will vary depend-
ing on outdoor temperature and moisture
conditions. When the defrost cycle is com-
plete the unit will return to normal heating
operation.
*Factory settings 9-30k Btu = 90 min
-
utes, 36k Btu = 60 minutes

Related product manuals