EMS 5000 FIREPOINT
ENGINEERS OPERATING GUIDE, ISSUE 3.0 – 16/08/10
23
11. How To Put Detector Zones Into Test (Testing Devices)
To put zones into test for the 5000 FirePoint, insert the key into the Panels Control Key
switch, located at the right of the panel. Turn the key to the “ON” position.
Step Action Screen Display
No
1
With the key in the “ON” position, the screen
will display:
2
Press the “0” key and the screen will now
display:
3
Press the “YES” key and the screen will now
display:
4
Press the “YES” key and the screen will now
display:
5
Enter 221100 and press the “YES” key and the
screen will now display:
6 Press Any key and the screen will
now display:
7 Press the “∇” key until the screen displays:
8 Press the “YES” key and the screen will now
display:
9 Press the “∇” key until the screen displays:
10 Press the “YES” key and the screen will now
display:
Panel in Access
|***Options **** |
> Passwords <
| Time and Date |
|** Fire system ** |
> Dev. Disable /Test<
| Net. Disable /Test |
Yes= Select Time
| Net. Disable /Test |
> Det Zone. Dis /Test <
| Alarm Zone Disable |
Yes= Select Time
| ** Zone Status ** |
> Zone is: 01 <
| Status : ACTIVE |
Yes= Select Time
| *PIN’s and ACCESS*|
>User Log ON <
| View Users |
Yes =Select Time
Enter Your PIN
To Log On > _
Then Press YES
Time
******************* *
Welcome Engineer *
Push Any Key Time
| Logging |
> Fire System Opts <
| Remote Access |
Yes= Select Time
|***Options **** |
> Passwords <
| Time and Date |