EMS 5000 FIREPOINT
ENGINEERS OPERATING GUIDE, ISSUE 3.0 – 16/08/10
31
12
Press the “YES” key to toggle though the
device numbers until you get to the
sounder that requires testing. (e.g. 025)
13
Press the “∇” key once and the screen will
display:
14
Press the “YES” key to toggle though the
different types of action commands. (E.g.
press the “YES” key seven times takes you to
test
)
There are 11 different types of actions: -
a
EVAC:
The selected sounder will activate with the evac tone.
b
ALERT
The selected sounder will activate with the warning
tone.
C
BOMB
The selected sounder will activate with the bomb tone.
D
LESS CHNG
The selected sounder will do a set of lesson change
beeps.
E
AUX ON
Not Used.
ALL OFF
The selected sounder will stop sounding. (I.e. Silence).
G
RX TEST
The receiver in the selected sounder will be sent a test
message, the sounder will receive the message and send
an acknowledgement message back to the 5000 panel.
H
TEST
The selected sounder will sound for four seconds and
then turn off. The sounder will listen to it self and send
an acknowledgement message back to the 5000 panel.
I
SET SYS
The 5000 panel will send a message to the selected
sounder, which sets the system code in the selected
sounder. The sounder then sends an acknowledgement
message back to the 5000 panel.
J
JOIN GRP
The 5000 panel will send the zone information to the
selected sounder, the selected sounder sends an
acknowledgement back to the 5000 panel.
K
SET LS CH
The 5000 panel will send a message to the selected
sounder which enables the lesson change, feature for the
device.
15 Press the “∇” key once and the screen will
display:
16 Press the “YES” key and the screen will now
display:
|** Configure ** |
>Sounder : 025 <
|Action : EVAC |
Yes= Select Time
| Sounder : 025 |
>Action : EVAC <
| Do Action |
Yes= Select Time
| Sounder : 025 |
>Action : TEST <
| Do Action |
Yes= Select Time
| Action : TEST |
>Do Action <
| ^^^^^^^^^^^^^^^ |
Yes= Select Time
Device 025 Timer 9
Retry 07 REPLY NONE
Push Any Key Time