ENCO Control
Technical description
Kulautuvos g. 45a , LT-47190 Kaunas Tel. (+370 37) 360234 Faks. (+370 37) 360358 info@axis.lt www.axis.lt
17
Table 11. Numbering of terminals
Terminal
number
Marking
Description
Permissible line
length, m
1
Input
230V ,
100mA Max
L1
Mains power supply 230V АС, L1
2
N
Mains power supply 230V АС, Neutral
3
Protective earthling
4
Battery 12 V
800 mA
B-
Battery (-)
<= 3 m
5
B+
Battery (+)
<= 3 m
6
Semiconductor
relays (NO)
O6-O8
230 V, 50Hz
1,2A each, Total
current for all
relays
4 A Max
O6
O6
Power output 6
<= 3 m
7
8
O7
O7
Power output 7
<= 3 m
9
10
O8
O8
Power output 8
<= 3 m
11
12
Discrete inputs
D0-D3
0-24 ,
15 mA Max
D0-
D0+
Discrete input 0 ( -)
<= 10 m
13
Discrete input 0 (+)
14
D1-
D1+
Discrete input 1 ( -)
<= 10 m
15
Discrete input 1 (+)
16
D2-
D2+
Discrete input 2 ( -)
<= 10 m
17
Discrete input 2 (+)
18
D3-
D3+
Discrete input 3 ( -)
<= 10 m
19
Discrete input 3 (+)
20
15 V,
100 mA
max
GND
Ground
<= 10 m
21
V+
Power supply output for external devices
<z= 10 m
22
RFID Antenna
R1
Antenna RFID
<= 0,3 m
23
R2
24
T sensor
GND
GND for digital temperature sensors
<= 70 m
25
DATA
Signal terminal for digital temperature sensors
<= 70 m
26
+5 V
+ 5 V power supply voltage for digital
temperature sensors
<= 70 m
27
Analog inputs
A0-A3
4-20 mA
A3
Analog input 3 for pressure sensor
<= 3 m
28
GND
Ground
<= 3 m
29
A2
Analog input 2 for pressure sensor
<= 3 m
30
GND
Ground
<= 10 m
31
A1
Analog input 1 for pressure sensor
<= 3 m
32
Outpu
t
+15 V
Power supply for external devices
(15V, to up 80 mA.)
<= 10 m
33
A0
Analog input 0 for pressure sensor
<= 3 m
34
Output
0-15 V
50 mA max
OL0
DO0-15V / AO 4-20 mA (Analog output is
galvanically isolated)
<= 3 m
35
GND
Ground
<= 3 m
36
OL1
DO0-15V / AO 4-20 mA (Analog output is
galvanically isolated)
<= 3 m
37
Mbus/CL
Cl-
<= 20 m