ENDA PLC PROGRAMMABLE LOGIC CONTROLOR
USER'S MANUAL
1) To avoid damaging the system, do not connect/disconnect the device when power
is on.
2) Make wiring according to user manual to avoid damaging the system.
3) Do not touch live wires.
4) Make sure the ground connection is wired.
5) CE Market according to European Norms.
ELC-186RT PLC unit has got support 8 digital input, 2 relay output, 4 Transistor output.
I/O capacity can extend to 256 point with expansion modules.
PLC parts and description
1 100Mb Ethernet port 10 Digital input terminal
2 RS485 serial port 11 IO status LEDs
3 RS232 serial port 12 Digital output terminals
4 PLC power status LED 13 Label area
5 PLC error status LED 14 DIN Ray installation flange
6 Program RUN status LED 15 Expansion modul BUS connector.
7 Reset button 16
8 Power supply terminal 17
9 DIN Ray installation flange
Technical Specification
Name Part Description
General
Power supply 24VDC, ±15% tolerans
Power
consumption
3WMax.
CPU process speed 80ns/command
Program language Graphical Ladder diagram with EndaSoft software.
Program capasity 48kB (Complied code)
Commands Logic, mathematical, communication, fast counter and timers, function blocks processed.
Communication
ports
Ethernet port 100MB ethernet port for PC programming and network connections. Connection through
the and programmable feature.
RS232 Serial port, MODBUS RTU protocol support
RS485 Serial port, MODBUS RTU protocol support
Input/Output Digital outputs 2 channels 220V 3A relay output, 4 channels pnp 24VDC transistor output, (QP2 and QP4
are high speed output max 100kHz)
Digital inputs 8 channels 24VDC pnp, 5mA connection, Logic 1 for >14VDC, Logic 0 for < 13VDC
Memory
Integer registers 1024 signed registers
Float registers 1024 signed float 32 registers
Counters 256 counters 32 bit up/down cunter
Timers 128 timer with 1ms resolution, 4 type timers
System registers 128 signed registers for accessing system properties
Environmental
conditions
Temperature -10..+60C (without icing)
Humidity 5..95rH nem
Do not use the device in locations subject to corrosive or flammable gasses.
Please read this document carefully before using this products! The guarantee will be
invalidated if the device is damaged by not following instructions detailed in the manual.
The company shall not be responsible for any damage or losses however caused, which
may be experienced as a result of the installation or use of this product.