CFR • HOT WATER COIL DATA
24
CFR Catalog • ©December, 2005 Environmental Technologies, Inc.
NOTES:
1. Data is based on 180°F entering water and 65°F entering air temperature at sea level. See selection procedure for other conditions.
2. For optimum diffuser performance in overhead heating applications, the supply air temperature should be within 20°F of the desired space
temperature. This typically requires a higher air capacity which provides higher air motion in the space, increasing thermal comfort. The hot
water coil should be selected with this in mind, keeping the LAT as low as possible.
The ENVIRO-TEC
®
Windows
®
based Computer Selection Program is available through your ENVIRO-TEC
®
representative for complete CFR
selection and hot water coil performance data.
1 Row 2 Row 1 Row 2 Row 1 Row 2 Row 1 Row 2 Row
0.5 0.3 0.1 115.0 135.7 157.8 148.6 5.4 7.7
1 1.0 0.3 120.3 144.6 167.7 162.3 6.0 8.6
2 3.5 1.0 123.5 149.8 173.5 170.6 6.3 9.2
3 7.5 2.1 124.7 151.7 175.6 173.6 6.5 9.4
4 12.7 3.5 125.4 152.7 176.6 175.1 6.5 9.5
5 -- 5.3 -- 153.3 -- 176.1 -- 9.6
0.5 0.3 0.1 105.7 123.2 152.9 141.4 6.6 9.5
1 1.0 0.3 111.3 133.3 164.6 157.2 7.5 11.1
2 3.5 1.0 114.8 139.7 171.7 167.5 8.1 12.1
3 7.5 2.1 116.1 142.2 174.3 171.4 8.3 12.5
4 12.7 3.5 116.8 143.4 175.7 173.4 8.4 12.7
5 -- 5.3 -- 144.3 -- 174.7 -- 12.9
0.5 0.3 0.1 99.7 114.5 149.2 136.2 7.5 10.7
1 1.0 0.3 105.2 125.1 162.1 153.3 8.7 13.0
2 3.5 1.0 108.9 132.2 170.2 165.1 9.5 14.6
3 7.5 2.1 110.3 135.0 173.3 169.6 9.8 15.2
4 12.7 3.5 111.0 136.5 174.9 172.0 10.0 15.5
5 -- 5.3 -- 137.4 -- 173.5 -- 15.7
0.5 0.3 0.1 95.4 108.2 146.3 132.3 8.2 11.7
1 1.0 0.3 100.9 118.8 160.1 150.1 9.7 14.6
2 3.5 1.0 104.5 126.3 169.0 163.0 10.7 16.6
3 7.5 2.1 106.0 129.3 172.4 168.1 11.1 17.4
4 12.7 3.5 106.7 130.9 174.2 170.8 11.3 17.8
5 -- 5.3 -- 131.9 -- 172.5 -- 18.1
0.5 0.3 0.1 92.2 103.3 143.9 129.2 8.8 12.5
1 1.0 0.3 97.5 113.8 158.4 147.5 10.6 15.9
2 3.6 1.0 101.1 121.5 167.9 161.2 11.7 18.4
3 7.5 2.1 102.6 124.6 171.6 166.7 12.2 19.4
4 12.7 3.5 103.4 126.3 173.6 169.8 12.5 19.9
5 -- 5.3 -- 127.4 -- 171.7 -- 20.3
0.5 0.3 0.1 89.6 99.5 141.9 126.7 9.3 13.1
1 1.0 0.3 94.8 109.8 156.9 145.3 11.3 17.0
2 3.6 1.0 98.4 117.5 167.0 159.6 12.7 19.9
3 7.5 2.1 99.9 120.7 170.9 165.5 13.2 21.1
4 12.7 3.6 100.7 122.5 173.0 168.8 13.5 21.8
5 -- 5.3 -- 123.7 -- 170.9 -- 22.2
0.5 0.3 0.1 87.5 96.4 140.1 124.6 9.7 13.6
1 1.0 0.3 92.5 106.4 155.5 143.3 11.9 17.9
2 3.6 1.0 96.1 114.1 166.1 158.2 13.5 21.3
3 7.5 2.1 97.6 117.4 170.3 164.5 14.1 22.7
4 12.7 3.6 98.4 119.2 172.6 167.9 14.5 23.5
5 -- 5.3 -- 120.4 -- 170.1 -- 24.0
CAPACITY
(MBH)
LWT (°F)
LAT (°F)
1 Row 0.01
2 Row 0.01
AIRFLOW
WATER FLOW
100
Rate
(CFM)
Air PD
(IN. W.G.)
Rate
(GPM)
Water PD (FT. W.G.)
300
1 Row 0.04
2 Row 0.08
200
1 Row 0.02
2 Row 0.04
250
1 Row 0.03
2 Row 0.06
150
1 Row 0.01
2 Row 0.02
350
1 Row 0.05
2 Row 0.11
400
1 Row 0.07
2 Row 0.14
MODEL CFR-WC • UNIT SIZES 0404, 0504, 0604