EO Genius & EO Hub Installation Guide
© EO Charging 2021 9
2.0
The installer should select the
RCD and earthing conguration
in accordance with the IET
Code of Practice and local
regulations.
Note: Where the EO Genius
includes DC leakage protection
(DCL) a Type A RCD can be
tted at the supply. Otherwise
a Type B RCBO or equivalent
should be used. EO recommend
a dedicated 40A supply rated
circuit for each charging station.
2.12
Important Installation Information
Characteristics of power supply input Permanently connected to 230/400V AC supply
Characteristics of power supply output Supplies 230V AC to the vehicle
Normal environmental conditions Can be installed indoors or outdoors
Access requirements Can be installed with no access restrictions
Mounting method
Stationary equipment intended for surface or post
mounting
Protection against electric shock Class II equipment
Charging mode (MODE 3)
DO NOT USE: Adaptors, converters and cord
extensions with this device
Ventilation during supply of energy Does not support ventilation during charging