SCOPE OF SUPPLY
• Foraccuratemeasurementitisessentialthatthetemperatureoftheprobeandmainlyofthesensingheadissameasthe
temperatureoftheairtomeasure.
• AvoidmountingtheEE150transmitterinawaywhichcreatestemperaturegradientsalongtheprobe.Ifpossible,EE150shall
beinstalledwiththeentireprobeinsidetheduct.Forinstallationwithmountingflange,incaseofdifferenttemperatureinside
andoutsidetheduct,theprobepartoutsidetheductshallbethermallyisolated.
• Thedeviceandmainlythesensingheadshallnotbeexposedtoextrememechanicalstress.
• Donotattempttoremovethefilercap,whichisfixed.Avoidtouchingthesensingheadatalltimes.
• ThestainlesssteelprobeisESDsensitiveandshallbehandledassuch.Donotconnectittothegroundpotential.
CAUtiOn
USER‘S GUIDE
COnnECtiOn diAgrAm
EE150 - Humidity and Temperature Transmitter for HVAC applications
5
6
(class III)
(class III)
T-passive connection
for HT3xxx/HT6xxx
EE150-HT3xxx
EE150-HT6xxx
dimEnSiOnS / mOUnting
CABLE GLAND M16x1.5
80.8 (3.18)
56 (2.2)
63 (2.48)
55.3 (2.18)
39.5 (1.56)
ø 5 (ø 0.2)
ø 4 (ø 0.16)
ø 6
(ø 0.24)
ø 7
(ø 0.28)
28.55
(1.12)
200
(7.87)
drilled hole for
mounting: ø>9 (ø>0.35)
Dimensions: mm (inch)
setupandadjustmentinterface(withEE-PCA)
setupandadjustmentinterface(withEE-PCA)
• EE150transmitter,typenumberaccordingtoorder(fororderingguideseedatasheetatwww.epluse.com/EE150)
• CableglandM16x1.5
• Mountingflange,PC,Ø6.0mm
• TestreportaccordingtoDINEN10204–2.2