1. SPECIFICATIONS.
Input:
Sampling period:
330 ms
230V~ ±15% or 12V=/~, max 3VA
Operating conditions: -5...60°C; 0...85%RH (non-condensing)
Storage conditions: -40...85°C; 0...85%RH (non-condensing)
Power supply:
two temperature sensors: NTC 5k by 25°C
bistate input (normally opened or normally closed)
Measuring accuracy: ±0,5%
Display resolutio: 0,1°C in whole range
Control form:
ON-OFF with hysteresis
Display:
LED, 4 digits, 11mm height with graphic icons
Protection class:
Ip20 / II
Measuring range:: -50...+150°C
Setting resolution: 0,1°C in whole range
2
2. OUTPUTS CARRYING CAPACITY.
11.2. Domestic hot water circuit circulation pump and central heating circuit pump control system.
11
Output: Relay:
Maximum resistive
load (for example heater):
Maximum inductive
load (for example engine):
30A 250V~
5
10 cycles
20A, 4500W
8A, 1500W, 2HP(2KM)
8A 250V~
5
10 cycles
8A, 1500W
2A, 400W, 0.5HP(0.5KM)
OUTPUT1
OUTPUT2
3. FRONT PANEL.
temperature setting signalling
OUTPUT1 signalling. LIGHTS: output active; BLINKS: output waits for start-up
OUTPUT2 signalling. LIGHTS: min or max temperature value exceeded (see: F15 or F16);
BLINKS: output waits for start-up (see: F17)
temperature display
temperature sensor number
entry to the parameters menu
temperature setting button
value increasing button
value decreasing button
emergency states signalling
Functions performed by the controller in the system:
- domestic hot water circulating pump and central heating
pump control system.
Tips for parameters programming:
F10=1 (container T1 and boiler T2 temp measurement)
F11=setting specifying the boiler temperature growth in
relation to the container temperature so that the domestic
hot water pump switches on, for example 8 °C
F12=DHW pump switching hysteresis, for example. 2 C
F15=given water temperature in the container. DHW pump
has a priority, so that only after reaching this setting, central
heating pump switches on, for example 60 °C
F16=OFF; F17=0.1; F21=0; F29=COOL ; F50=0 ; F51=0
F52=0 (when central heating pump switches on, domestic
hot water pump switches off)
°
F12=2°C
F12=2°C
6°C
8°C
Main
output
Time
Time
Temp.
0
1
10°C
Auxiliary
output
when T1>F15
1
T2-T1
Time
0
F11
SC-20
T1 - boiler temperature sensor
T2 - fireplace temperature sensor
Collector pump and c.h. pump max. 400W 230V~
Power supply
230V~
20(8)A 8(2)A
T2
Pk
Pco
1314 15161211
D
M
set
Pch
Pdhw
Cold
water
T2
T1
Boiler
M
set