1. Visually inspect the LED test switch (LTS) monthly. It should be illuminated when AC power is applied, check status
conditions (see section titled "LED Test Switch Conditions" below).
2. Conduct a 60-second discharge test, which can be initiated via the LED Test Switch (see section titled "Manual Test"
below) or by switching OFF the emergency breaker for 60-seconds. Check status conditions (see section titled "LED
TEST SWITCH CONDITIONS" below).
3. Conduct a 90-minute discharge test annually, which can be initiated via the LED Test Switch (see section titled "Manual
Test" Below) or by switching OFF the emergency breaker for 90 minutes. Check status conditions (see section titled "LED
TEST SWITCH CONDITIONS" below).
1. INITIAL SELF-TEST
When the system is connected properly and powered on (make sure the load is switched on), the MIP-36 will perform
an Initial SELF-TEST. If any abnormal conditions exist, the LTS will blink quickly. Once the abnormal condition is
corrected, the LTS will function correctly. The Initial Self Test will be restarted automatically when the connected
dimmable loads' maximum power increases.
2. PREPROGRAMMED SCHEDULED SELF-TEST
a) The unit will conduct the first Monthly SELF-TEST
after 24 hours and up to 7 days after initial power on. Then
monthly tests will be performed every 30 days.
b) Annual SELF-TEST will occur every 52 weeks after initial power on.
- MONTHLY SELF-TEST
The Monthly SELF-TEST shall be executed every 30 days, and will test:
Normal to emergency transfer function, emergency, charging and discharging conditions are normal. Monthly test time
is approximately 60 seconds.
- ANNUAL SELF-TEST
Annual SELF-TEST will occur every 52 weeks after the initial 24 hours full charge, and will test:
Proper initial battery voltage, 90-minute emergency operation and acceptable battery voltage at the end of the full 90-
minute test.
If the SELF-TEST is interrupted by a power failure, a full 90-minute SELF-TEST will occur again 24 hours after the
power is restored. If the power failure causes the battery to fully discharge, the product will restart the Initial SELF-
TEST and Preprogrammed Scheduled SELF-TEST.
- MANUAL TEST
1. Press the LTS one time to simulate emergency mode for 10 seconds.
2. Press the LTS 2 times continuously within 3 seconds to force a 60-second monthly test. After the test is completed, the next
(30-day) monthly test will count from this date.
3. Press the LTS 3 times continuously within 3 seconds to force a 90-minute annual test.
After the test is completed, the next
(52-week) annual test will count from this date. Note - the product must be 24-hour fully charged.
4.
In normal mode, press and hold the LTS for greater than 3 seconds to restart Initial SELF-TEST.
5. During any manual test, press and hold the LTS for greater than 3 seconds to terminate a manual test. The Preprogrammed
Scheduled SELF-TEST Test will not change.
LED TEST SWITCH CONDITIONS
LTS Slow Blinking: Normal Charging
LTS On: Battery Fully Charged - Normal Condition
LTS Off: Power Failure
LTS Gradual Change: In Testing Mode
LTS Quickly Blinking: Abnormal Condition - Corrective Action Required
SELF-TEST STATUS
On initial power on or after a battery reset, if the SELF-
TEST is enabled, the LTS (LED
test switch) will blink 3 times (on 0.3
seconds and off 0.3 seconds), and then stay off for 2 seconds. The LTS will return to normal mode (slow blinking during
charging, continuously on once fully charged); If the SELF-TEST is disabled, the LTS will blink 6 times (on 0.3 seconds and
off 0.3 seconds) and then stay off for 2 seconds. The LTS will return to normal mode (slow blinking during charging,
continuously on once fully charged).
DISABLING/ENABLING SELF-TEST:
During normal operation, press the LTS 5 times within 3 seconds. If the SELF-TEST was previously enabled, the signal light
will blink 6 times (on 0.3 seconds, off 0.3 seconds) and then stay off for 2 seconds. After 3 cycles of this display, the LTS will
return to normal mode (slow blinking during charging, continuously on once fully charged), and the SELF-TEST will be
disabled. If the SELF-TEST was previously disabled, the LTS will blink 3 times (on 0.3 seconds and off 0.3 seconds) and then
stay off for 2 seconds. After 3 cycles of this display, the LTS will return to normal mode (slow blinking during charging,
continuously on once fully charged) and the SELF-TEST will be enabled.
OPERATION / TESTING / MAINTENANCE
OPERATION
When AC power is applied, the LED test switch is illuminated, indicating that the batteries are being charged. When AC
power fails, the MIP-36 automatically switches to emergency power, operating the lighting load at rated emergency
power. During power failure, the LED test switch will be off. When the AC power is restored, the MIP-36 switches the
system back to normal mode of operation and resumes battery charging.
The minimum emergency operation time is 90 minutes. A short term discharge test may be conducted after unit has been
charging for 1 hour. The charging time for the full discharged battery of MIP-36 is 12 hours.
TESTING AND MAINTENANCE
The following Periodic testing is recommended to ensure the system is working correctly.