1. The MIP-36 requires an unswitched AC power supply of 120-277 volt, 50/60Hz.
2. Refer to the wiring diagrams below. Make connections in the following order 1 2 3 4 5 6 7 8
3. Consult the factory for other wiring diagrams.
WIRING DIAGRAMS
EVENLITE WWW.EVENLITE.COM
REV-1 
Z410205
3
CAUTION: DO NOT MATE BROWN WIRE UNIT CONNECTOR UNTIL INSTALLATION IS
COMPLETE AND AC POWER IS SUPPLIED.
MIP-36
MIP-36
NON-EMERGENCY LUMINAIRES
WIRING DIAGRAM FOR NON-DIMMABLE EMERGENCY LIGHTING SYSTEM
WIRING DIAGRAM FOR 0-10V DIMMABLE EMERGENCY LIGHTING SYSTEM
MAX. LOAD = 36W
BLACK
BLACK/ORANGE
GREEN/YELLOW
WHITE
NEUTRAL
GROUND
HOT
LED Test Switch
120-277V AC
LED
FLUORESCENT
INCANDESCENT
LUMINAIRE
YELLOW (+)
YELLOW/BLACK (-)
YELLOW (+)
YELLOW/BLACK (-)
D
IM IN VIOLET (+)
DIM IN PINK (-)
WHITE/ORANGE (OUT NEUTRAL)
120-277V AC
ORANGE (OUT HOT)
BROWN
LED
FLUORESCENT
INCANDESCENT
LUMINAIRE
0-10V
DIMMER
DIM OUT VIOLET/BLACK (+)
DIM OUT PINK/BLACK (-)
Cap unused leads
BLACK
BLACK/ORANGE
GREEN/YELLOW
WHITE
NEUTRAL
GROUND
SWITCH
HOT
120-277V AC
LED
FLUORESCENT
INCANDESCENT
LUMINAIRE
DIM I
N VIOLET (+)
DIM IN PINK (-)
LED Test Switch
WHITE/ORANGE (OUT NEUTRAL)
120-277V AC
ORANGE (OUT HOT)
BROWN
LED
FLUORESCENT
INCANDESCENT
LUMINAIRE
Cap unused leads
DIM OUT VIOLET/BLACK (+)
DIM OUT PINK/BLACK (-)
YELLOW/BLACK (-)
YELLOW (+)
YELLOW/BLACK (-)
YELLOW (+)
LED
FLUORESCENT
INCANDESCENT
WITH LUMINAIRE
EMERGENCY
BACKUP
LED
FLUORESCENT
INCANDESCENT
WITH LUMINAIRE
EMERGENCY
BACKUP
LED
FLUORESCENT
INCANDESCENT
WITH LUMINAIRE
EMERGENCY
BACKUP
LED
FLUORESCENT
INCANDESCENT
WITH LUMINAIRE
EMERGENCY
BACKUP
SWITCHED
+
-
NOTE: THE MAX. LINKABLE LUMINAIRE QUANTITY IN EMERGENCY MODE MAY VARY DUE TO
LUMINAIRE ELECTRICAL CHARACTERISTICS. ACTUAL LOAD MUST BE VERIFIED BY END USER.
BROWN
CAUTION: BROWN WIRE UNIT CONNECTOR ENERGIZES INVERTER-
CONNECT LAST AND
ALWAYS DISCONNECT BEFORE SERVICING
BROWN
CAUTION: BROWN WIRE UNIT
CONNECTOR ENERGIZES INVERTER-
CONNECT LAST AND ALWAYS DISCONNECT BEFORE SERVICING
MAX. DIMMABLE LOAD = 360 W (PF of load >/=0.9)
LUMINAIRES WITH DIMMED EMERGENCY BACKUP
UNIT CONNECTOR
NON-EMERGENCY LUMINAIRES
LUMINAIRES WITH EMERGENCY BACKUP
UNIT CONNECTOR