SET 0 (ST-0)
SET 0 has four sublevels:
pb, ti, td
and
cy
.
pb
: Proportional valve of process.
ti
: Integral process time.
td
: Process derived
cy
: Process action cicle
SET 1 (ST-1)
SET 1 has two sublevels:
Db.cl
and
Crcl
.
Db.cl: Cooling on delay (factory set at 2).
Example: Set temperature value: 80
o
C
Db.cl set at 2 will energise the cooling solenoid valve at 82
o
C.
Crcl : Cooling relative gain ( factory set at 0,4 )
If the cooling water is from one chiller you can change it to a 0,2.
to allow change datas press
and the first digit to be set will flash modify
it with
keys press to confirm.
SET 2 (ST-2)
Internal adjustment, non accessible.
SET 3 (ST-3)
SET 3 has three sublevels :
AO.H, AO.L
and
AO.S
AO.H High oulet tension limit 4-20mA
AO.L Low oulet tension limit 4-20mA
AO.S Sign oulet tension limit 4-20mA
Only for units working with
current loop
system.