EasyManua.ls Logo

Everwarm EW18NM - Page 10

Default Icon
25 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10
Figure 4 - Heat resistant material
(slate, marble, tile, etc.) above
replace
Heat Resistant
Material
If Using Mantel
You must have noncombustible material(s) (such as slate, marble, tile, etc). at least 1/2 in. thick. With sheet metal,
you must have noncombustible material behind it. Noncombustible material must extend at least 8 inches up. If
noncombustible material is less than 12 in., you must install the replace hood accessory. Even if noncombustible
material is more than 12 in., you may need the hood accessory to deect heat away from mantel shelf. See Figures
4, 5 and 6 for minimum clearances requirements.
IMPORTANT: If these minimum clearances are not met, you must operate heater with chimney ue damper
open. Go to “Installing Damper Clamp Accessory for Vented Operation,” page 11.
Noncombustible
Material Distance
Requirements for
Safe Installation
8 inches or more Noncombustible material okay.
Less than 8 inches Noncombustible material must be
extended to at least 8 inches. See be-
tween 8 inches and 12 inches above. If
you can not extend material, you must
operate heater with ue damper open.
MANTEL CLEARANCES
In addition to meeting noncombustible
material clearances, you must also meet
required clearances between replace
opening and mantel shelf. If the clearances
listed below are not met, you will need a
hood.
Determining Mantel Clearances
If you meet minimum clearance
requirements between mantel shelf and top of
replace opening, a hood is not necessary
(see Figure 5).
Determining Minimum Mantel Clearance
When Using a Hood
If minimum clearances in Figure 5 are not met,
you must have a hood. When using a hood
there are still certain minimum mantel clearances
required. Follow minimum clearances shown in
Figure 6 when using a hood.
NOTICE: Surface temperature of adjacent walls
and mantels become hot during operation. Walls and
mantels above the rebox may become too hot to
touch. If installed properly, thes temperatures meet the
requirement of the national product standard. Follow
all minimum clearances shown in this manual.
NOTICE: If your installation does not meet the minimum
clearances shown, you must do one of the following:
Operate the logs with the ue damper open only.
Raise the mantel to an acceptable height.
FLOOR CLEARANCES
a) If installing appliance on oor level, you must maintain
the minimum distance of 14 inches to combustibles
(see Figure 7).
b) If combustible materials are less than 14 inches to the
replace, you must install appliance at least 5 inches
above the combustible ooring (see Figure 8 ).
24” Model
Figure 5- Minimum mantel
clearances without using hood
Log set
18” Model
Top of Fireplace
Opening
Underside of
Mantel Shelf
A l l m i n i m u m
distances are in
inches
Mantel Shelf
Minimum Non-
Combustible Material
Distances to
Underside of
Mantel
Minimum Non-
Combustible
Material Height

Related product manuals