1
Battery Specifications
Battery Dimensions
Terminal Dimensions
Features
Overview
The ExpertPower EP48100 battery is
optimized to be a high energy density storage
solution for commercial or residential use; our
modular solution allows parallel connections
of up to 51.2KWH and discharge of 100A per
battery for large commercial applications.
• RS485 communication for computer monitor-
ing.
• Built-in BMS with automatic protection for a
variety of conditions.
• Built-in cell by cell monitoring
• Convenient modular approach for easy
replacement and maintenance.
• A+ grade cells for reliable and long lasting
power
19
7
18.9
50
20
mm
28
NOMINAL CHARACTERISTICS
MECHANICAL CHARACTERISTICS
ELECTRICAL CHARACTERISTICS
OPERATION CONDITIONS
GENERAL INFORMATION
Nominal Voltage
Normal Energy ( 77°F, 0.2C )
Terminal
Weight
Dimensions ( L x W x H )
Nominal Capacity ( 77°F, 0.2C )
Max. Charge Current
Max. Constant Discharge Current
Charge Voltage
Cut-o Voltage
Charging Standard
Estimated Life ( 77°F )
Cycle Life ( 0.2C, 77°F )
Operating Temperature
Storage Time / Temperature
51.2 V
5120 Wh
100 Ah
M6
98 lbs
19 x 18.9 x 7 in
100 A
56 V
50 A
40 V
CC: 0.2C to 56 V
CV: 56 V
Floating: 55.2 V - 56 V
Charging end current: 0.01C
> 10 Years
8000 with 50% DOD
4000 with 80% DOD
3000 with 100% DOD
Charging: 32 - 131°F
Discharging: -4 - 131°F
Less than 18 months at -4 - 77°F
Less than 12 months at 25 - 95°F
Less than 3 months at 95 - 131°F
Casing Material
Assembly
Recommended Charging Type
BMS
Steel
16S1P - Single cell Capacity 100Ah
CC - CV - Float charge
Integrated with LCD display