48VFL & 96VFL v1.2 07/13
Symptom Probable Solution
- Sensor break error
- Sensor not connected
- Replace sensor
- Check that the sensor is connected correctly
- A/D converter damage
- Unit must be repaired or replaced
- Check for outside source of damage such as
transient voltage spikes
- Auto tune time out error Set Pb, ti, td manually
Keypad not
functioning
- Keypad is locked
- Keypad is defective
- Set”
”to an appropriate value
- Have unit repaired
Process
value
unstable
- Improper setting of Pb, Ti, Td and
CT
- Start AT process to set Pb, Ti, Td automatically
- Set Pb, Ti, Td manually
No heat or
output
- No heater power or fuse open
- Output device defective or
incorrect output used
- Check output wiring and fuse
- Replace output device
LEDs and
display not
lighting up
- No power to controller
- SMPS failure
- Check power lines connection
- Replace or repair meter
Process
Value
changed
abnormally
- Electromagnetic Interference
(EMI) or Radio Frequency
Interference (RFI)
- Suppress arcing contacts in system to eliminate high
voltage spike sources. Separate the sensors and the
controller wiring from “noisy” power lines. Ground
heaters
Entered
data lost
- EEPROM error - Replace or repair meter
w ww. . com
information@itm.com1.800.561.8187

Other manuals for Extech Instruments VFL Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Extech Instruments VFL Series and is the answer not in the manual?

Extech Instruments VFL Series Specifications

General IconGeneral
BrandExtech Instruments
ModelVFL Series
CategoryController
LanguageEnglish

Related product manuals