TM2 PP M 9 A4516_6G38_Rev.A
- To prevent any danger or malfunction, the size of electrical control components
connected to the motor must be compatible with the electrical features of the
motor.
- Means for disconnection must be incorporated in the fixed wiring in accordance
with the national installation standards.
- The selectors inverting the direction of rotation of the motor must be provided
with mechanical interlocking.
- Invert the brown and the black conductor to change the direction of rotation.
- NEVER connect two or more selectors to the same motor.
- For outdoor use, provide the appliance with a supply cable with designation
H05RN-F containing at least 2% of carbon.
- Cable length between motor and control-switch maximal 50 m. In case of cable
length more than 50 m an interface-relay have to be used.
ELECTRICAL CONNECTIONS
TRANSLATION OF THE ORIGINAL INSTRUCTIONS