Power supplies
2.
Ref.1912
· 69 ·
DDS
HARDWARE
Note prior to installation
Before installing an RPS power supply when using NON-FAGOR motors,
remember that:
MANDATORY.
Any element that will be part of the drive-motor system powered by an RPS
must meet the isolation requirements described in EN 61800-5-1.
All the components connected to the intermediate circuit must run
permanently on a voltage higher than 625 V in the intermediate circuit.
The motor temperature sensor must also comply with EN 61800-5-1.
RECOMMENDATION.
Configure the RPS power supply with the minimum bus voltage to
satisfactorily meet the features required by the system.